Yaskawa F7 Drive Programming Manual User Manual

Page 21

Advertising
background image

Programming 13

b2-02 DC Injection Braking Current

Setting Range:

0 to 100%

Factory Default: 50%

The level of DC Injection Braking Current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the level of current will increase the amount of heat generated by the motor windings and should only be increased
to the level necessary to hold the motor shaft. DC Injection current is set in percentage of Drive rated output current. Drive
rated output current is stated on the Drive nameplate.

b2-03 DC Injection Braking Time at Start

b2-04 DC Injection Braking Time at Stop

Setting Range:

0.00 to 10.00 Seconds

Factory Default: 0.00 Seconds

The Drive can be programmed to automatically DC Inject for a predetermined amount of time prior to accelerating to speed
(b2-03) and/or at the end of a Ramp to stop (b2-04). Parameter b2-03 can be used to stop a rotating motor prior to attempting
acceleration (i.e. a wind milling fan). If DC Injection braking at start or Speed Search is not enabled, attempting to drive a
spinning motor may cause nuisance tripping.

Parameter b2-04 can be used to resist any residual motion of the load after the deceleration has finished.

Fig. 9 DC Injection Braking During Starting and stopping

Parameter b2-04 also serves the function of affecting the length of time DC Injection to stop (b1-03= “2: DC Injection to
Stop”) will occur.

b2-08 Magnetic Flux Compensation Capacity

Setting Range:

0 to 1000%

Factory Default: 0%

This parameter allows the magnetizing motor flux to be boosted when starting the motor. This parameter will facilitate a quick
ramp-up of the torque reference and magnetizing current reference to reduce motor slip during start. A setting of 100% equals
motor no-load current E2-03. This flux level will be applied below Minimum Output Frequency (E1-09) until the DC Injection
Time at Start (b2-03) expires. This parameter is useful when starting motors that are relatively larger than the Drive, due to the
requirement for increased magnetizing current. This parameter may also compensate for reduced starting torque due to motor
circuit inefficiencies.

Output Frequency

DC injection

b2-03 b2-04

Advertising