Programming 31

C3-04 Slip Compensation Selection During Regeneration

Determines whether slip compensation is enabled or disabled during regenerative operation.

C3-05 Output Voltage Limit Operation Selection

Determines if the motor flux is automatically decreased when output voltage saturation occurs in the constant horsepower region.

C4 Torque Compensation

C4-01 Torque Compensation Gain

Setting Range:

0.00 to 2.50

Factory Default: 1.00

C4-02 Torque Compensation Primary Delay Time

Setting Range:

0 to 10000 ms

Factory Default: 200 ms

The Torque Compensation function compensates for insufficient torque production at start-up and during low speed operation.
The Drive will detect increases in the motor load by monitoring the output current and compensate by increasing the output
voltage. The increased output voltage leads to an increase in usable torque.

Parameter C4-01 sets the aggressiveness of the compensation for IR (resistive) and IL (inductive) losses in the motor windings,
which are more pronounced at lower speeds. Normally C4-01 does not need to be changed but may require adjustment in the
following cases:

If the Drive to motor cable is long, increase C4-01

If the motor capacity is smaller than the Drive capacity, increase C4-01

If the low speed motor performance is unstable, decrease C4-01.

If the output current level exceeds the Drive’s rated current while operating at low speeds, increase C4-01

Parameter C4-02 determines how quickly the Torque Compensation function will react to situations of insufficient torque.
Again, C4-02 will not normally require adjustment except for the following situations:

If the motor vibrates, increase C4-02

If the motor response is sluggish (and possibly stalls), decrease C4-02

Note: Default factory setting will be 200 ms when parameter A1-02=0 (V/f control without PG) or 1 (V/f control with PG).

When parameter A1-02=2 (Open Loop Vector) the default factory setting will be 20 ms.

Setting

Description

0

Disabled (factory default)

1

Enabled

Setting

Description

0

Disabled (factory default)

1

Enabled

IMPORTANT

Performing Auto-tuning can enhance low speed performance.