1) overview, 2) format – Yaskawa MP2000 Series: User's Manual for Motion Programming User Manual

Page 263

Advertising
background image

8 Command Reference

8.9.15 OFF-Delay Timer (TOF):Counting unit: 0.01 second

8-156

8.9.15 OFF-Delay Timer (TOF):Counting unit: 0.01 second

(1) Overview

The TOF command counts the milliseconds (in units of 10 ms) when the bit input is OFF. When the counted
value is equal to the set value, the bit output will turn OFF. If the bit input turns ON during counting, the timer
operation will stop. After the bit input turns OFF again, counting starts again from the beginning (0). In the regis-
ters for counting, the actual count (in units of 10 ms) is stored.

Note: The following versions of system software and programming tool MPE720 are required to use TOF

commands.

(2) Format

• Milliseconds are not counted while the debugging operation is stopped.

Counting starts again from the current counted value after the debugging operation restarts.

• Be sure to designate bit input “DBxxxxxx&.”

Motion Programs

Sequence Programs

Not applicable

Applicable

MP2000 Series

Machine Controller

Required Version

MPE720

Required Version

All models

Ver. 2.60 or later

MPE720 Ver.5

MPE720 Ver.5.38 or later

MPE720 Ver.6

MPE720 Ver.6.04 or later
MPE720 Ver.6.04Lite or later

DB000001 = DB000000 & TOF (500 DW00001);

A B C D

Item

Description

Usable Registers

A

Bit output

• Bit type registers (Excluding # and C registers)
• The above registers with subscript

B

Bit input

• All bit type registers
• The above registers with subscript

C

Set value

• All integer type registers
• The above registers with subscript
• Constants (0 to 65535 (655.35 s): Every 10 ms)

D

Register for timer counting

• All integer type registers
• The above registers with subscript

IMPORTANT

Advertising