Flange Type Models 4A0930 and 4A1200
n
Flange Type Exterior and Mounting Dimensions
HORIZONTAL MOUNTING DIM
M16 THREAD
NOTE: Maximum surrounding air temperature is 50 °C (122 °F)
(6) EXTERNAL
COOLING FANS
LIFTING AND EYEBOLT DETAILS
(20) MOUNTING HOLES
FOR 1/2 in. [M12] SCREWS
Unit: in. [mm]
NOTE: Spreader bar required to avoid damage during lifting.
FRONT VIEW
VER
TICAL
MOUNTING DIM
(2)-MOUNTING BRACKETS
USED DURING TRANSPORT ONLY
REMOVE BEFORE INSTALLING
Figure 2.60 Models 4A0930 and 4A1200
n
Flange Type Heat Loss Data
Table 2.30 Models 4A0930 and 4A1200
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
4A0930
400
2952
8476
11428
2455
6912
9367
575 (1265)
4A1200
3612
8572
12184
3155
7626
10781
587 (1291)
2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss