Three-Phase 600 V Class Drive Models 5A0003 to 5A0032

Table A.8 Power Ratings (Three-Phase 600 V Class)

Item

Specification

Drive Models

5A0003 5A0004 5A0006 5A0009 5A0011 5A0017 5A0022 5A0027 5A0032

Maximum Applicable Motor

Capacity (HP)

<1>

ND Rating

2

3

5

7.5

10

15

20

25

30

HD Rating

1

2

3

5

7.5

10

15

20

25

Input

Input Current (A)

<2>

ND Rating

3.6

5.1

8.3

12

16

23

31

38

45

HD Rating

1.9

3.6

5.1

8.3

12

16

23

31

38

Rated Voltage

Rated Frequency

Three-phase 500 to 600 Vac 50/60 Hz

Allowable Voltage Fluctuation

-10 (-15) to +10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

ND Rating

4.1

5.8

9.5

14

18

26

35

43

51

HD Rating

2.2

4.1

5.8

9.5

14

18

26

35

43

Output

Rated Output

Capacity (kVA)

<3>

ND Rating

<4>

2.7

3.9

6.1

9

11

17

22

27

32

HD Rating

<5>

1.7

3.5

4.1

6.3

9.8

12

17

22

27

Rated Output

Current (A)

ND Rating

<4>

2.7

3.9

6.1

9

11

17

22

27

32

HD Rating

<5>

1.7

3.5

4.1

6.3

9.8

12.5

17

22

27

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

HD Rating: 150% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

User adjustable between 2 and 15 kHz

User adjustable between 2 and 10 kHz

Maximum Output Voltage (V)

Three-phase 500 to 600 Vac (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.