Yaskawa CIMR-AU 200V Drives User Manual

Page 301

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F7-21

(03F9)

EtherNet/IP Voltage

Scaling Factor

EN Voltage Scale

Sets the scaling factor for the voltage monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-22

(03FA)

EtherNet/IP Time

Scaling

EN Time Scale

Sets the scaling factor for the time monitor in EtherNet/IP Class

ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-23 to

F7-32

(03FB to

0374)

Dynamic Output

Assembly Parameters

Parameters used in Output Assembly 116. Each parameter

contains a MEMOBUS/Modbus address. The value received

for Output Assembly 116 will be written to this corresponding

MEMOBUS/Modbus address. A MEMOBUS/Modbus

address value of 0 means that the value received for Output

Assembly 116 will not be written to any MEMOBUS/Modbus

register.

Default: 0

F7-33 to

F7-42

(0375 to

037E)

Dynamic Input

Assembly Parameters

Parameters used in Input Assembly 166. Each parameter

contains a MEMOBUS/Modbus address. The value sent for

Input Assembly 166 will be read from this corresponding

MEMOBUS/Modbus address. A MEMOBUS/Modbus

address value of 0 means that the value sent for Input Assembly

166 is not defined by the user, therefore the option default

register value will be returned.

Default: 0

<1> Cycle power for setting changes to take effect.
<2> If F7-13 is set to 0, then all IP Addresses (as defined with parameters F7-01 to F7-04) must be unique.

B.6 F: Options

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

301

B

Parameter List