Yaskawa CIMR-AU 200V Drives User Manual

Page 307

Advertising
background image

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

E

Fault

Fault

Closed: Fault occurred (this excludes CPF00 and CPF01).

F

Through mode

Not Used

Select this setting when the terminal is not used or when using the terminal in the

pass-through mode.

10

Minor fault

Minor Fault

Closed: An alarm has been triggered, or the IGBTs have reached 90% of their

expected life span.

11

Fault reset command

active

Reset Cmd Active

Closed: The drive has received a reset command from the multi-function input

terminals or from a serial network, or the RESET key on the digital operator has

been pressed.

12

Timer output

Timer Output

Closed: Timer output.

13

Speed agree 2

Fref/Fout Agree2

Closed: When drive output frequency equals the frequency reference ±L4-04.

Note:

This setting is not available in models 4A0930 and 4A1200.

14

User-set speed agree 2

Fref/Set Agree 2

Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.

15

Frequency detection 3

Freq Detect 3

Closed: When the drive output frequency is less than or equal to the value in L4-03

±L4-04.

16

Frequency detection 4

Freq Detect 4

Closed: When the output frequency is greater than or equal to the value in L4-03

±L4-04.

17

Torque detection 1

(N.C.)

Trq Det 1 N.C.

Open: Overtorque or undertorque has been detected.

18

Torque detection 2

(N.O.)

Trq Det 2 N.O.

Closed: Overtorque or undertorque has been detected.

19

Torque detection 2

(N.C.)

Trq Det 2 N.C.

Open: Overtorque or undertorque has been detected.

1A

During reverse

Reverse Dir

Closed: Drive is running in the reverse direction.

1B

During baseblock (N.C.) BaseBlk 2

Open: Drive has entered the baseblock state (no output voltage).

1C

Motor 2 selection

Motor 2 Selected

Closed: Motor 2 is selected by a digital input (H1-oo = 16)

1D

During regeneration

Regenerating

Closed: Motor is regenerating energy into the drive.

1E

Restart enabled

Dur Flt Restart

Closed: An automatic restart is performed

1F

Motor overload alarm

(oL1)

Overload (OL1)

Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers

this alarm.

20

Drive overheat pre-

alarm (oH)

OH Prealarm

Closed: Heatsink temperature exceeds the parameter L8-02 value.

22

Mechanical weakening

detection

MechFatigue(OL5)

Closed: Mechanical weakening detected.

2F

Maintenance period

Maintenance

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay

may require maintenance.

30

During torque limit

Torque Limit

Closed: When the torque limit has been reached.

31

During speed limit

Speed Limit

Closed: Speed limit has been reached.

32

During speed limit in

Torque Control

Spd Lim @ T Cont

Closed: Speed limit has been reached while using Torque Control.

33

Zero Servo complete

Zero Servo End

Closed: Zero Servo operation has finished.

37

During frequency output During RUN 2

Open: No frequency output from drive if stopped with baseblock, DC injection

braking during initial excitation, or short-circuit braking.

Closed: Drive is outputting a frequency.

38

Drive enabled

Drive Enable

Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)

39

Watt hour pulse output Watt-hour Pulse

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate

the kWh count.

3C

LOCAL/REMOTE

status

Local

Open: REMOTE

Closed: LOCAL

3D

During speed search

During SpdSrch

Closed: Speed Search is being executed.

3E

PID feedback low

PID Feedback Low

Closed: PID feedback level is too low.

3F

PID feedback high

PID FeedbackHigh

Closed: The PID feedback level is too high.

4A

During KEB Ride-Thru During KEB

Closed: KEB Ride-Thru is being performed.

4B

During short circuit

braking

During SC Brake

Closed: Short Circuit Braking is active.

B.7 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

307

B

Parameter List

Advertising