Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4A0208
R/L1, S/L2, T/L3
300
2 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
300
2 to 300
⊖, ⊕1
–
1 to 250
⊕3
–
3 to 3/0
4
4 to 300
4A0250
R/L1, S/L2, T/L3
400
1 to 600
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
400
1/0 to 600
⊖, ⊕1
–
3/0 to 600
⊕3
–
1 to 325
2
2 to 350
4A0296
R/L1, S/L2, T/L3
500
2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
500
2/0 to 600
⊖, ⊕1
–
3/0 to 600
⊕3
–
1 to 325
M10
18 to 23
(159 to 204)
2
2 to 350
M12
32 to 40
(283 to 354)
4A0362
R/L1, S/L2, T/L3
4/0 × 2P
3/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0 × 2P
3/0 to 600
⊖, ⊕1
–
4/0 to 600
⊕3
–
3/0 to 600
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
4A0414
R/L1, S/L2, T/L3
300 × 2P
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300 × 2P
4/0 to 300
⊖, ⊕1
–
3/0 to 300
⊕3
–
3/0 to 300
1
1 to 3/0
4A0515
R/L1, S/L2, T/L3
3/0 × 4P
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0 × 4P
3/0 to 300
⊖, ⊕1
–
1/0 to 300
⊕3
–
1/0 to 300
1/0
1/0 to 300
4A0675
R/L1, S/L2, T/L3
300 × 4P
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300 × 4P
4/0 to 300
⊖, ⊕1
–
1/0 to 300
⊕3
–
1/0 to 300
2/0
2/0 to 300
4A0930
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
4/0 × 4P×2
3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
4/0 × 4P×2
3/0 to 300
⊖, ⊕1
–
4/0 to 300
⊕3
–
4/0 to 300
3/0
3/0 to 250
4A1200
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
300 × 4P×2
4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
300 × 4P×2
4/0 to 300
⊖, ⊕1
–
250 to 300
⊕3
–
4/0 to 300
4/0
4/0 to 250
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.