5.3 Alarm Detection

u

Alarm Codes, Causes, and Possible Solutions

Alarms are drive protection functions that do not necessarily cause the drive to stop. After removing the cause of an alarm,

the drive will return to the same status is was before the alarm occurred.
When an alarm has been triggered, the ALM light on the digital operator display blinks and the alarm code display flashes. If

a multi-function output is set for an alarm (H2-oo = 10), that output terminal will be triggered.

Note:

If a multi-function output is set to close when an alarm occurs (H2-oo = 10), it will also close when maintenance periods are reached,

triggering alarms LT-1 through LT-4 (triggered only if H2-oo = 2F).

Table 5.3 Alarm Codes, Causes, and Possible Solutions

Digital Operator Display

Minor Fault Name

AEr

Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside of the acceptable setting range.

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

boL

Braking Transistor Overload Fault
The braking transistor in the drive has been overloaded.

bUS

Option Communication Error
• The connection was lost after initial communication was established.
• Assign a Run command frequency reference to the option.

CALL

Serial Communication Transmission Error
Communication has not yet been established.

CE

MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.

CrST

Cannot Reset

CyC

MECHATROLINK Comm. Cycle Setting Error
Comm. Cycle Setting Error was detected.

dEv

Speed Deviation (when using a PG option card and OLV/PM without PG)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer

than the time in F1-11.

dnE

Drive Disabled

EF

Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.

EF0

Option Card External Fault
An external fault condition is present.

EF1

External Fault (Input Terminal S1)
External fault at multi-function input terminal S1.

EF2

External fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External fault (input terminal S4)
External fault at multi-function input terminal S4.

5.3 Alarm Detection

214