H4: analog outputs – Yaskawa CIMR-AU 200V Drives User Manual

Page 310

Advertising
background image

H3 Multi-Function Analog Input Settings

H3-oo

Setting

Function

LCD Display

Description When Output Is 100%

Page

C

PID setpoint

PID Set Point

10 V = 100%

D

Frequency bias

Freq Ref Bias 2

10 V = E1-04 (maximum output frequency)

E

Motor temperature

(PTC input)

Motor PTC

10 V = 100%

F

Through mode

Not Used

Select this setting when the terminal is not used or when using the terminal in the

pass-through mode.

10

Forward torque limit

Fwd Torque Limit

10 V = Motor rated torque

11

Reverse torque limit

Rev Torque Limit

10 V = Motor rated torque

12

Regenerative torque

limit

Regen Torq Limit

10 V = Motor rated torque

13

Torque reference/

Torque limit

Torque Reference

10 V = Motor rated torque

14

Torque compensation

Torque Comp

10 V = Motor rated torque

15

General torque limit

Torque Limit

10 V = Motor rated torque

16

Differential PID

feedback

PID Feedback 2

10 V = 100%

17

Motor Thermistor

(NTC)

Moter temp (NTC)

10 V = -9 °C

0 V = +234 °C

Note:

This setting is only available in models 4A0930 and 4A1200.

1F

Through mode

Not Used

Select this setting when the terminal is not used or when using the terminal in the

pass-through mode.

30 to 32 DriveWorksEZ

analog input 1 to 3

Output is determined by the function selected using DWEZ.

u

H4: Analog Outputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H4-01

(041D)

Multi-Function Analog

Output Terminal FM

Monitor Selection

Term FM FuncSel

Selects the data to be output through multi-function analog

output terminal FM.

Set the desired monitor parameter to the digits available in

Uo-oo.

For example, enter “103” for U1-03.

Default: 102

Range: 000 to

999

180

H4-02

(041E)

Multi-Function Analog

Output Terminal FM

Gain

Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the

selected monitor value.

Default: 100.0%

Min.: -999.9

Max.: 999.9

181

H4-03

(041F)

Multi-Function Analog

Output Terminal FM

Bias

Terminal FM Bias

Sets the signal level at terminal FM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

181

H4-04

(0420)

Multi-Function Analog

Output Terminal AM

Monitor Selection

Terminal AM Sel

Selects the data to be output through multi-function analog

output terminal AM.

Set the desired monitor parameter to the digits available in

Uo-oo.

For example, enter “103” for U1-03.

Default: 103

Range: 000 to

999

180

H4-05

(0421)

Multi-Function Analog

Output Terminal AM

Gain

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of

the selected monitor value.

Default: 50.0%

Min.: -999.9

Max.: 999.9

181

H4-06

(0422)

Multi-Function Analog

Output Terminal AM

Bias

Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

181

H4-07

(0423)

Multi-Function Analog

Output Terminal FM

Signal Level Selection

Term FM Lvl Sel

0: 0-10 VDC

1: -10 +10 VDC

2: 4-20 mA

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

Default: 0

Range: 0 to 2

182

B.7 H Parameters: Multi-Function Terminals

310

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide