H6: pulse train input/output – Yaskawa CIMR-AU 200V Drives User Manual

Page 312

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H5-17

(11A1)

<2>

Operation Selection

when Unable to Write

into EEPROM

Busy Enter Sel

0: No ROM Enter

1: RAM Enter

Selects operation when an attempt is made to write data into

EEPROM via MEMOBUS/Modbus communications and

writing into EEPROM is not possible.

There is normally no need to change this parameter from the

default value

0: Cannot write into EEPROM

1: Write in RAM only

Note:

Parameter is not available in models 4A0930 and

4A1200.

Default: 0

Range: 0, 1

H5-18

(11A2)

<3>

Filter Time Constant for

Motor Speed Monitoring MtrSpd Monitor T

Sets the filter time constant for monitoring the motor speed

from MEMOBUS/Modbus communications and

communication options.

Applicable MEMOBUS/Modbus registers are: 3EH, 3FH,

44H, ACH, and ADH

Note:

Parameter is not available in models 4A0930 and

4A1200.

Default: 0 ms

Min.: 0

Max.: 100

<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<2> Available in drive software versions PRG: 1018 and later.
<3> Available in drive software versions PRG: 1019 and later.

u

H6: Pulse Train Input/Output

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H6-01

(042C)

Pulse Train Input

Terminal RP Function

Selection

Term RP Func Sel

0: Frequency Ref

1: PID Feedback

2: PID Set Point

3: PG Feedback

0: Frequency reference

1: PID feedback value

2: PID setpoint value

3: V/f Control with Simple PG feedback (possible only when

using motor 1 in V/f Control)

Default: 0

Range: 0 to 3

H6-02

(042D) Pulse Train Input

Scaling

Term RP Scaling

Sets the terminal RP input signal frequency that is equal to

100% of the value selected in H6-01.

Default: 1440 Hz

Min.: 100

Max.: 32000

H6-03

(042E) Pulse Train Input Gain Terminal RP Gain

Sets the level of the value selected in H6-01 when a frequency

with the value set in H6-02 is input.

Default: 100.0%

Min.: 0.0

Max.: 1000.0

H6-04

(042F) Pulse Train Input Bias

Terminal RP Bias

Sets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%

Min.: -100.0

Max.: 100.0

H6-05

(0430) Pulse Train Input Filter

Time

Term RP Flt Time

Sets the pulse train input filter time constant.

Default: 0.10 s

Min.: 0.00

Max.: 2.00

H6-06

(0431) Pulse Train Monitor

Selection

Term MP Func Sel

Select the pulse train monitor output function (value of the

o-oo part of Uo-oo).

For example, enter “501” for U5-01.

Default: 102

Range: 000 to 809

H6-07

(0432) Pulse Train Monitor

Scaling

Term RP Scaling

Sets the terminal MP output signal frequency when the monitor

value is 100%.

For example, to have the pulse train monitor output equal the

output frequency, set H6-06 to 102 and H6-07 to 0.

Default: 1440 Hz

Min.: 0

Max.: 32000

H6-08

(043F)

Pulse Train Input

Minimum Frequency

MP Lower Limit

Sets the minimum frequency for the pulse train input to be

detected. Enabled when H6-01 = 0, 1, or 2.

Default: 0.5 Hz

Min.: 0.1

Max.: 1000.0

B.7 H Parameters: Multi-Function Terminals

312

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide