C.1 european standards, Ce low voltage directive compliance, Area of use – Yaskawa CIMR-AU 200V Drives User Manual

Page 346: Factory recommended branch circuit protection

Advertising
background image

C.1 European Standards

Figure C.1 CE Mark

The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business

and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics

manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
Low Voltage Directive: 2006/95/EC
EMC Guidelines: 2004/108/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying

the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE

standards. After setting up the device, verify that conditions meet European standards.

Note:

600 V class drives (models 5oooooo) are not compliant with European Standards.

u

CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage

Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other

devices:

n

Area of Use

Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.

n

Factory Recommended Branch Circuit Protection

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in

Table C.1

.

NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices

to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.

Table C.1 Factory Recommended Drive Branch Circuit Protection

Drive Model

Fuse Type

Manufacturer: Bussmann

Model

Fuse Ampere Rating (A)

Three-Phase 200 V Class

2A0004

FWH-70B

70

2A0006

FWH-70B

70

2A0008

FWH-70B

70

2A0010

FWH-70B

70

2A0012

FWH-70B

70

2A0018

FWH-90B

90

2A0021

FWH-90B

90

2A0030

FWH-100B

100

2A0040

FWH-200B

200

2A0056

FWH-200B

200

2A0069

FWH-200B

200

2A0081

FWH-300A

300

2A0110

FWH-300A

300

C.1 European Standards

346

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide