Yaskawa CIMR-AU 200V Drives User Manual

Page 72

Advertising
background image

(2) GROUND
TERMINALS

SECTION B-B

CONTROL CIRCUIT
TERMINALS

MAIN CIRCUIT
TERMINALS

Unit: in. [mm]

0.94

[23.9]

Figure 2.34 Model 4T0072

Table 2.19 12-Pulse Model 4T0072Terminal and Wire Specifications for Main Circuit and Ground

Drive Model

Terminal

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4T0072

<1>

R/L1, S/L2, T/L3

10 to 3/0 (5.3 to 85.0)

M8

9 to 11

(79.7 to 97.4)

R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
B1, B2

22 to 10 (0.3 to 5.3)

M4

1.2 (10.6)

Refer to applicable codes for wire size

M8

9 to 11

(79.7 to 97.4)

<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.