No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H4-08

(0424)

Multi-Function Analog

Output Terminal AM

Signal Level Selection

Term AM Lvl Sel

0: 0-10 VDC

1: -10 +10 VDC

2: 4-20 mA

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

Default: 0

Range: 0 to 2

182

u

H5: MEMOBUS/Modbus Serial Communication

Note:

Restart the drive to enable MEMOBUS/Modbus communication settings.

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H5-01

(0425)

<1>

Drive Node Address

Serial Comm Adr

Selects drive station node number (address) for MEMOBUS/

Modbus terminals R+, R-, S+, S-. Cycle power for the setting

to take effect.

Default: 1F (Hex)

Min.: 0

Max.: FF

H5-02

(0426)

Communication Speed

Selection

Serial Baud Rate

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19.2 kbps

5: 38.4 kbps

6: 57.6 kbps

7: 76.8 kbps

8: 115.2 kbps

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Cycle power for the setting to take effect.

Default: 3

Range: 0 to 8

H5-03

(0427)

Communication Parity

Selection

Serial Com Sel

0: No Parity

1: Even Parity

2: Odd Parity

0: No parity

1: Even parity

2: Odd parity

Cycle power for the setting to take effect.

Default: 0

Range: 0 to 2

H5-04

(0428)

Stopping Method after

Communication Error

(CE)

Serial Fault Sel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop

1: Coast to stop

2: Fast Stop

3: Alarm only

Default: 3

Range: 0 to 3

H5-05

(0429)

Communication Fault

Detection Selection

Serial Flt Dtct

0: Disabled

1: Enabled

0: Disabled

1: Enabled. If communication is lost for more than two seconds,

a CE fault will occur.

Default: 1

Range: 0, 1

H5-06

(042A)

Drive Transmit Wait

Time

Transmit WaitTIM

Set the wait time between receiving and sending data.

Default: 5 ms

Min.: 5

Max.: 65

H5-07

(042B) RTS Control Selection

RTS Control Sel

0: Disabled

1: Enabled

0: Disabled. RTS is always on.

1: Enabled. RTS turns on only when sending.

Default: 1

Range: 0, 1

H5-09

(0435) CE Detection Time

CE Detect Time

Sets the time required to detect a communications error.

Adjustment may be needed when networking several drives.

Default: 2.0 s

Min.: 0.0

Max.: 10.0

H5-10

(0436)

Unit Selection for

MEMOBUS/Modbus

Register 0025H

CommReg 25h Unit

0: 0.1 V

1: 1 V

0: 0.1 V units

1: 1 V units

Default: 0

Range: 0, 1

H5-11

(043C)

Communications

ENTER Function

Selection

Enter CommandSel

0: Enter Required

1: No EnterRequired

0: Drive requires an Enter command before accepting any

changes to parameter settings.

1: Parameter changes are activated immediately without the

Enter command (same as V7).

Default: 0

Range: 0, 1

H5-12

(043D)

Run Command Method

Selection

Run CommandSel

0: FWD Run &REV

Run

1: Run & FWD/REV

0: FWD/Stop, REV/Stop

1: Run/Stop, FWD/REV

Default: 0

Range: 0, 1

B.7 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

311

B

Parameter List