Yaskawa CIMR-AU 200V Drives User Manual

Page 203

Advertising
background image

CPF25

Terminal Board Not Connected

to

to

CPF26 to CPF35

CPF40 to CPF45

Control Circuit Error
CPU error

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

dEv

Speed Deviation (for Control Mode with PG and OLV/PM without PG)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for

longer than the time set to F1-11.

dv1

Z Pulse Fault (CLV/PM control mode only)
The motor turned one full rotation without the Z Pulse being detected.

dv2

Z Pulse Noise Fault Detection (CLV/PM control mode only)
The Z Pulse is out of phase by more than 5 degrees for 10 consecutive revolutions.

dv3

Inversion Detection (CLV/PM control mode only)
The torque reference and acceleration are in opposite directions and the speed reference and actual motor

speed differ by more than 30% for the number of times set to F1-18.

dv4

Inversion Prevention Detection (CLV/PM control mode only)
Pulses indicate that the motor is rotating in the opposite direction of the speed reference. Set the number

of pulses to trigger inverse detection to F1-19.

Note:

Set F1-19 to 0 to disable inverse detection in applications where the motor may rotate in

the opposite direction of the speed reference.

<1>

dv7

Initial Polarity Estimation Timeout

<1> Available in drive software versions PRG: 1015 and later.

dWAL

DriveWorksEZ Fault

dWFL

Digital Operator Display

Fault Name

dWF1

EEPROM Memory DriveWorksEZ Data Error
There is an error in the DriveWorksEZ program saved to EEPROM.

E5

MECHATROLINK Watchdog Timer Error
The watchdog timed out.

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the PLC

and F6-03 is set to a value other than 3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

Digital Operator Display

Fault Name

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External Fault (input terminal S3)
External fault at multi-function input terminal S3.

5.2 Fault Detection

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

203

5

Troubleshooting