u

b5: PID Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-01

(01A5) PID Function Setting

PID Mode

0: Disabled

1: Enabled D=Fdbk

2: Enabled D=Fdfwd

3: Fref+PID D=Fdbk

4: Fref+PID D=Fdfwd

5: Enabled D=Fdbk2

6: Enabled D=Fdfwd2

7: Fref+PID D=Fdbk2

8: Fref

+PIDD=Fdfwd2

0: Disabled

1: Enabled (PID output becomes output frequency reference,

deviation D controlled)

2: Enabled (PID output becomes output frequency reference,

feedback D controlled)

3: Enabled (PID output added to frequency reference, deviation

D controlled)

4: Enabled (PID output added to frequency reference, feedback

D controlled)

5: Mode compatible with setting 1 of similar products from a

previous product line

6: Mode compatible with setting 2 of similar products from a

previous product line

7: Mode compatible with setting 3 of similar products from a

previous product line

8: Mode compatible with setting 4 of similar products from a

previous product line

Note:

1. If the drive is replaced with Varispeed F7

drive or a similar product from a previous

product line, use settings 5 to 8 instead of

settings 1 to 4.

2. Settings 5 to 8 are not available in models

4A0930 and 4A1200.

Default: 0

<1>

Range: 0 to 8

<2>

b5-02

(01A6) Proportional Gain

Setting (P)

PID Gain

Sets the proportional gain of the PID controller.

Default: 1.00

Min.: 0.00

Max.: 25.00

b5-03

(01A7) Integral Time Setting (I) PID I Time

Sets the integral time for the PID controller.

Default: 1.0 s

Min.: 0.0

Max.: 360.0

b5-04

(01A8) Integral Limit Setting

PID I Limit

Sets the maximum output possible from the integrator as a

percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

b5-05

(01A9) Derivative Time (D)

PID D Time

Sets D control derivative time.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

b5-06

(01AA) PID Output Limit

PID Limit

Sets the maximum output possible from the entire PID

controller as a percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

b5-07

(01AB) PID Offset Adjustment PID Offset

Applies an offset to the PID controller output. Set as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

b5-08

(01AC) PID Primary Delay Time

Constant

PID Delay Time

Sets a low pass filter time constant on the output of the PID

controller.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

b5-09

(01AD)

PID Output Level

Selection

Output Level Sel

0: Normal Character

1: Rev Character

0: Normal output (direct acting)

1: Reverse output (reverse acting)

Default: 0

Range: 0, 1

b5-10

(01AE) PID Output Gain Setting Output Gain

Sets the gain applied to the PID output.

Note:

Parameter setting cannot be changed when the

drive is operating the motor in models 4A0930

and 4A1200.

Default: 1.00

Min.: 0.00

Max.: 25.00

b5-11

(01AF)

PID Output Reverse

Selection

Output Rev Sel

0: 0 limit

1: Reverse

0: Negative PID output triggers zero limit.

1: Rotation direction reverses with negative PID output.

Note:

When using setting 1, make sure reverse

operation is permitted by b1-04.

Default: 0

Range: 0, 1

B.2 b: Application