There is a problem with the voltage from the

drive input power

• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main

circuit magnetic contactor.

The power has been interrupted

Correct the drive input power.

The main circuit capacitors are worn

• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

The relay or contactor on the soft-charge

bypass relay is damaged

• Cycle power to the drive and see if the fault reoccurs.
• Check monitor U4-06 for the performance life of the soft-charge bypass relay.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display

Fault Name

Uv2

Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.

Cause

Possible Solution

In drive models 2A0004 to 2A0056 or 4A0002

to 4A0031, L2-02 was changed from its

default value without installing a Momentary

Power Loss Ride-Thru unit

Correct the setting to L2-02 or install an optional Momentary Power Loss Ride-Thru unit.

Control power supply wiring is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the control board, the entire drive, or the control power supply. For

instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.

Internal circuitry is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display

Fault Name

Uv3

Undervoltage 3 (Soft-Charge Bypass Relay Fault)
The soft-charge bypass relay failed.

<1>

Uv4

Gate Drive Board Undervoltage
Voltage drop in the gate drive board circuit

<1> Detected in models 4A0930 and 4A1200.

voF

Output Voltage Detection Fault
Problem detected with the voltage on the output side of the drive.

5.2 Fault Detection

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide