2 main circuit connection diagram, Three-phase 200 v class models 2a0004 to 2a0081, Three-phase 200 v class models 2a0110, 2a0138 – Yaskawa CIMR-AU 200V Drives User Manual

Page 109: Main circuit connection diagram

Advertising
background image

3.2 Main Circuit Connection Diagram

Refer to diagrams in this section when wiring the main circuit of the drive. Connections may vary based on drive capacity.

The DC power supply for the main circuit also provides power to the control circuit.

NOTICE: Do not use the negative DC bus terminal “–” as a ground terminal. This terminal is at high DC voltage potential. Improper wiring

connections could damage the drive.

u

Three-Phase 200 V Class Models 2A0004 to 2A0081
Three-Phase 400 V Class Models 4A0002 to 4A0044
Three-Phase 600 V Class Models 5A0003 to 5A0032

+1

+2

R/L1

S/L2

T/L3

Relay

Gate board

Control

board

Operator

+

Current

sensor

U/T1
V/T2
W/T3

B1 B2

Figure 3.2 Connecting Main Circuit Terminals

u

Three-Phase 200 V Class Models 2A0110, 2A0138
Three-Phase 400 V Class Models 4A0058, 4A0072
Three-Phase 600 V Class Models 5A0041, 5A0052

+1

R/L1

S/L2

T/L3

U/T1
V/T2
W/T3

B1 B2

DC link

choke

+

Relay

Gate board

Control

board

Operator

Current

sensor

Figure 3.3 Connecting Main Circuit Terminals

3.2 Main Circuit Connection Diagram

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

109

3

Electrical Installation

Advertising