Motor Application Precautions

n

Standard Induction Motors

Low-Speed Range

The cooling fan of a standard motor should sufficiently cool the motor at the rated speed. As the self-cooling capability of

such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. Reduce the load torque

as the motor slows to prevent motor damage from overheat.

Figure i.2

shows the allowable load characteristics for a Yaskawa

standard motor. Use a motor designed specifically for operation with a drive when 100% continuous torque is needed at low

speeds.

50

3 6

60

60

70

80

90

100

25% ED (or 15 min)

40% ED (or 20 min)

60% ED (or 40 min)

Frequency (Hz)

Continuous operation

Torque

(%)

20

Figure i.2 Allowable Load Characteristics for a Yaskawa Motor

Insulation Tolerance

NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly

long wiring distances.

High-Speed Operation

NOTICE: Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed.

Contact the motor or machine manufacturer.

Torque Characteristics

Torque characteristics differ compared to operating the motor directly from line power. The user should have a full

understanding of the load torque characteristics for the application.

Vibration and Shock

The drive allows selection of high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce

motor oscillation.
• Take particular caution when adding a variable speed drive to an application running a motor from line power at a constant

speed. If resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump frequency

selection to prevent continuous operation in the resonant frequency range.

• Mechanical resonance can occur with long motor shafts and in applications such as turbines, blowers, and fans with high

inertia loads. Use Closed Loop Vector Control when these applications experience mechanical resonance problems.

Audible Noise

The audible noise of the motor varies based on the carrier frequency setting. However, drive current derating may be required.

When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running

from line power.

n

Synchronous Motors

• Contact Yaskawa or a Yaskawa agent when planning to use a synchronous motor not endorsed by Yaskawa.
• Use a standard induction motor when running multiple synchronous motors simultaneously. A single drive does not have

this capability.

• A synchronous motor may rotate slightly in the opposite direction of the Run command at start depending on parameter

settings and rotor position.

• The amount of generated starting torque differs depending on the control mode and motor type. Set up the motor with the

drive after verifying the starting torque, allowable load characteristics, impact load tolerance, and speed control range.

i.2 General Safety

18