d3: Jump Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d3-01

(0294)

Jump Frequency 1

Jump Freq 1

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default:

<1> <2>

Min.: 0.0

<2>

Max.: 400.0

<2>

d3-02

(0295)

Jump Frequency 2

Jump Freq 2

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default:

<1> <2>

Min.: 0.0

<2>

Max.: 400.0

<2>

d3-03

(0296)

Jump Frequency 3

Jump Freq 3

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default:

<1> <2>

Min.: 0.0

<2>

Max.: 400.0

<2>

d3-04

(0297)

Jump Frequency Width Jump Bandwidth

Sets the dead-band width around each selected prohibited

frequency reference point.

Default:

<1> <3>

Min.: 0.0

<3>

Max.: 20.0

<3>

<1> Default setting is determined by parameter A1-02, Control Mode Setting.
<2> Default setting is 0.0% and setting range is 0.0 to 100.0% in AOLV/PM or CLV/PM.
<3> Default setting is 1.0% and setting range is 0.0 to 40.0% in AOLV/PM and CLV/PM.

u

d4: Frequency Reference Hold and Up/Down 2 Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d4-01

(0298)

Frequency Reference

Hold Function Selection

Fref Hold Sel

0: Disabled

1: Enabled

0: Disabled. Drive starts from zero when the power is switched

on.

1: Enabled. At power up, the drive starts the motor at the Hold

frequency that was saved.

Default: 0

Range: 0, 1

d4-03

(02AA) Frequency Reference

Bias Step (Up/Down 2) Up/Dn 2 Step Lvl

Sets the bias added to the frequency reference when the Up 2

and Down 2 digital inputs are enabled (H1-oo = 75, 76).

Default: 0.00 Hz

Min.: 0.00

Max.: 99.99

d4-04

(02AB)

Frequency Reference

Bias Accel/Decel (Up/

Down 2)

Up/Dn 2 Ramp Sel

0: Sel Acc/Dec Time

1: Acc/Dec Time 4

0: Use selected accel/decel time.

1: Use accel/decel time 4 (C1-07 and C1-08).

Default: 0

Range: 0, 1

d4-05

(02AC)

Frequency Reference

Bias Operation Mode

Selection (Up/Down 2)

Up/Dn 2 Bias Sel

0: Hold Bias Value

1: Reset Bias Value

0: Bias value is held if no input Up 2 or Down 2 is active.

1: When the Up 2 reference and Down 2 reference are both on

or both off, the applied bias becomes 0. The specified accel/

decel times are used for acceleration or deceleration.

Default: 0

Range: 0, 1

d4-06

(02AD)

Frequency Reference

Bias (Up/Down 2)

Up/Dn 2 Bias Lvl

The Up/Down 2 bias value is saved in d4-06 when the

frequency reference is not input by the digital operator. Set as

a percentage of the maximum output frequency.

Default: 0.0%

Min.: -99.9

Max.: 100.0

d4-07

(02AE)

Analog Frequency

Reference Fluctuation

Limit (Up/Down 2)

Up/Dn 2 FluctLim

Limits how much the frequency reference is allowed to change

while an input terminal set for Up 2 or Down 2 is enabled. If

the frequency reference changes for more than the set value,

then the bias value is held and the drive accelerates or

decelerates to the frequency reference. Set as a percentage of

the maximum output frequency.

Default: 1.0%

Min.: 0.1

Max.: 100.0

d4-08

(02AF)

Frequency Reference

Bias Upper Limit (Up/

Down 2)

Up/Dn 2 UpperLim

Sets the upper limit for the bias and the value that can be saved

in d4-06. Set as a percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

d4-09

(02B0)

Frequency Reference

Bias Lower Limit (Up/

Down 2)

Up/Dn 2 LowerLim

Sets the lower limit for the bias and the value that can be saved

in d4-06. Set as a percentage of the maximum output frequency.

Default: 0.0%

Min.: -99.9

Max.: 0.0

B.4 d: References