3.7 Control Circuit Wiring

u

Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S8), multi-function digital outputs

(M1 to M6), multi-function analog inputs (A1 to A3), and multi-function analog monitor output (FM, AM). The default setting

is listed next to each terminal in

Figure 3.1

on page

107

.

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with

untested control circuits could result in death or serious injury.

WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter

A1-06 may change the I/O terminal function automatically from the factory setting.

Refer to Application Selection on page 157

. Failure

to comply may result in death or serious injury.

n

Input Terminals

Table 3.7

lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.

Table 3.7 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Multi-Function

Digital Inputs

S1

Multi-function input 1

(Closed: Forward run, Open: Stop)

• Photocoupler
• 24 Vdc, 8 mA

Refer to Sinking/Sourcing Mode for Digital Inputs on page

135

.

302

S2

Multi-function input 2

(Closed: Reverse run, Open: Stop)

S3

Multi-function input 3

(External fault, N.O.)

S4

Multi-function input 4

(Fault reset)

S5

Multi-function input 5

(Multi-step speed reference 1)

S6

Multi-function input 6

(Multi-step speed reference 2)

S7

Multi-function input 7

(Jog reference)

S8

Multi-function input 8

(Baseblock command (N.O.))

SC

Multi-function input common

Multi-function input common

SP

Digital input power supply +24 Vdc

24 Vdc power supply for digital inputs, 150 mA max (only when not

using digital input option DI-A3)

NOTICE: Do not jumper or short terminals SP and SN. Failure

to comply will damage the drive.

135

SN

Digital input power supply 0 V

135

Safe Disable

Inputs

H1

Safe Disable input 1

<1>

• 24 Vdc, 8 mA
• One or both open: Output disabled
• Both closed: Normal operation
• Internal impedance: 3.3 kΩ
• Off time of at least 1 ms
• Disconnect the wire jumpers shorting terminals H1, H2, and HC to

use the Safe Disable inputs. Set the S3 jumper to select between

sinking, sourcing mode, and the power supply as explained on page

135

.

368

H2

Safe Disable input 2

<1>

HC

Safe Disable function common

Safe disable function common

3.7 Control Circuit Wiring