Yaskawa CIMR-AU 200V Drives User Manual

Page 300

Advertising
background image

u

F7: Communication Option Card (SI-EM3, SI-EN3, SI-EP3)

F7 parameters are used for EtherNet/IP, Modbus TCP/IP, and PROFINET options. Other parameters in the F7 group are used

for communication-protocol-specific settings. For more details on a specific option card, refer to the instruction manual for

the option.

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F7-01

(03E5)

<1>

IP Address 1

IP Address 1

Sets the most significant octet of network static IP address.

Default: 192

Range: 0 to 255

F7-02

(03E6)

<1>

IP Address 2

IP Address 2

Sets the second most significant octet of network static IP

address.

Default: 168

Range: 0 to 255

F7-03

(03E7)

<1>

IP Address 3

IP Address 3

Sets the third most significant octet of network static IP

address.

Default: 1

Range: 0 to 255

F7-04

(03E8)

<1>

IP Address 4

IP Address 4

Sets the fourth most significant octet of network static IP

address.

Default: 20

Range: 0 to 255

F7-05

(03E9) Subnet Mask 1

Subnet Mask 1

Sets the most significant octet of network static Subnet Mask. Default: 255

Range: 0 to 255

F7-06

(03EA) Subnet Mask 2

Subnet Mask 2

Sets the second most significant octet of network static Subnet

Mask.

Default: 255

Range: 0 to 255

F7-07

(03EB) Subnet Mask 3

Subnet Mask 3

Sets the third most significant octet of network static Subnet

Mask.

Default: 255

Range: 0 to 255

F7-08

(03EC) Subnet Mask 4

Subnet Mask 4

Sets the fourth most significant octet of network static Subnet

Mask.

Default: 0

Range: 0 to 255

F7-09

(03ED) Gateway Address 1

Gateway IP Add 1

Sets the most significant octet of network Gateway address.

Default: 192

Range: 0 to 255

F7-10

(03EE) Gateway Address 2

Gateway IP Add 2

Sets the second most significant octet of network Gateway

address.

Default: 168

Range: 0 to 255

F7-11

(03EF) Gateway Address 3

Gateway IP Add 3

Sets the third most significant octet of network Gateway

address.

Default: 1

Range: 0 to 255

F7-12

(03E0) Gateway Address 4

Gateway IP Add 4

Sets the fourth most significant octet of network Gateway

address.

Default: 1

Range: 0 to 255

F7-13

(03F1) Address Mode at Startup

IP Add Mode Sel

0: User Defined

1: BOOTP

2: DHCP

Select the option address setting method
0: Static

<2>

1: BOOTP

2: DHCP

Default: 2

Range: 0 to 2

F7-14

(03F2) Duplex Mode Selection

Duplex Select

0: Half Duplex

1: Auto Negotiate

2: Full Duplex

Selects duplex mode setting.

0: Half duplex forced

1: Auto-negotiate duplex mode and communication speed

2: Full duplex forced

Default: 1

Range: 0 to 2

F7-15

(03F3)

Communication Speed

Selection

Baud Rate

10: 10 Mbps

100: 100 Mbps

Sets the communication speed

10: 10 Mbps

100: 100 Mbps

Default: 10

Range: 10, 100

F7-16

(03F4)

Communication Loss

Timeout

CommLoss Tout

Sets the timeout value for communication loss detection in

tenths of a second. A value of 0 disables the connection

timeout.

Example: An entered value of 100 represents 10.0 seconds.

Default: 0

Min.: 0

Max.: 300

F7-17

(03F5)

EtherNet/IP Speed

Scaling Factor

EN Speed Scale

Sets the scaling factor for the speed monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-18

(03F6)

EtherNet/IP Current

Scaling Factor

EN Current Scale

Sets the scaling factor for the output current monitor in

EtherNet/IP Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-19

(03F7)

EtherNet/IP Torque

Scaling Factor

EN Torque Scale

Sets the scaling factor for the torque monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-20

(03F8)

EtherNet/IP Power

Scaling Factor

EN Power Scale

Sets the scaling factor for the power monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

B.6 F: Options

300

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

Advertising