E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 200% of the drive

rated current

<1>

Determined by

C6-01 and o2-04

<1> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

Note:

An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly to

prevent this error.

n

H1-01 to H1-08: Functions for Terminals S1 to S8

These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in

Table

4.26

.

No.

Parameter Name

Setting

Range

Default

H1-01

Multi-Function Digital Input Terminal S1 Function Selection

1 to 9F

40 (F)

<1>

: Forward Run Command (2-Wire sequence)

H1-02

Multi-Function Digital Input Terminal S2 Function Selection

1 to 9F

41 (F)

<1>

: Reverse Run Command (2-Wire sequence)

H1-03

Multi-Function Digital Input Terminal S3 Function Selection

0 to 9F

24: External Fault

H1-04

Multi-Function Digital Input Terminal S4 Function Selection

0 to 9F

14: Fault Reset

H1-05

Multi-Function Digital Input Terminal S5 Function Selection

0 to 9F

3 (0)

<1>

: Multi-Step Speed Reference 1

H1-06

Multi-Function Digital Input Terminal S6 Function Selection

0 to 9F

4 (3)

<1>

: Multi-Step Speed Reference 2

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

0 to 9F

6 (4)

<1>

: Jog Reference Selection

H1-08

Multi-Function Digital Input Terminal S8 Function Selection

0 to 9F

8: External Baseblock Command

<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).

Table 4.26 Multi-Function Digital Input Terminal Settings

Setting

Function

Page

0

3-Wire Sequence

176

1

LOCAL/REMOTE Selection

2

External Reference 1/2 Selection

3

Multi-Step Speed Reference 1

4

Multi-Step Speed Reference 2

5

Multi-Step Speed Reference 3

6

Jog reference Selection

7

Accel/Decel Time Selection 1

8

Baseblock Command (N.O.)

9

Baseblock Command (N.C.)

A

Accel/Decel Ramp Hold

B

Drive Overheat Alarm (oH2)

C

Analog Terminal Input Selection

D

PG Encoder Disable

E

ASR integral reset

F

Through Mode

10

Up Command

11

Down Command

12

Forward Jog

13

Reverse Jog

14

Fault Reset

15

Fast Stop (N.O.)

Setting

Function

Page

16

Motor 2 Selection

17

Fast Stop (N.C.)

18

Timer Function Input

19

PID Disable

1A

Accel/Decel Time Selection 2

1B

Program Lockout

1E

Reference Sample Hold

20 to 2F External Fault

30

PID Integral Reset

31

PID Integral Hold

32

Multi-Step Speed Reference 4

34

PID Soft Starter Cancel

35

PID Input Level Selection

40

Forward Run Command (2-Wire sequence)

41

Reverse Run Command (2-Wire sequence)

42

Run Command (2-Wire sequence 2)

43

FWD/REV Command (2-Wire sequence 2)

44

Offset Frequency 1

45

Offset Frequency 2

46

Offset Frequency 3

47

Node Setup

60

DC Injection Braking Command

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

175

4

Start-Up Programming & Operation

Advertising