Yaskawa CIMR-AU 200V Drives User Manual

Page 298

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F6-25

(03C9)

Operation Selection at

MECHATROLINK

Watchdog Timer Error

(E5)

SI-T WDTErr Sel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop. Decelerate using the deceleration time in

C1-02.

1: Coast to stop

2: Fast stop. Decelerate using the deceleration time in C1-09.

3: Alarm only

Default: 1

Range: 0 to 3

F6-26

(03CA)

MECHATROLINK

bUS Errors Detected

Num of SI-T BUS

Sets the number of option communication errors (bUS).

Default: 2

Min.: 2

Max.: 10

F6-30

(03CB)

PROFIBUS-DP Node

Address

PB Node Address

Sets the node address.

Default: 0

Min.: 0

Max.: 125

F6-31

(03CC)

PROFIBUS-DP Clear

Mode Selection

PB Clear Select

0: Reset to Zero

1: Hold Prev Value

0: Resets drive operation with a Clear mode command.

1: Maintains the previous operation state when Clear mode

command is given.

Default: 0

Range: 0, 1

F6-32

(03CD)

PROFIBUS-DP Data

Format Selection

PB Map Select

0: PPO Type

1: Conventional

0: PPO Type

1: Conventional

Default: 0

Range: 0, 1

F6-35

(03D0)

CANopen Node ID

Selection

CO Node Address

Sets the node address.

Default: 0

Min.: 0

Max.: 126

F6-36

(03D1)

CANopen

Communication Speed

CO Baud Rate

0: Auto Detect

1: 10 kbps

2: 20 kbps

3: 50 kbps

4: 125 kbps

5: 250 kbps

6: 500 kbps

7: 800 kbps

8: 1Mbps

0: Auto-detection

1: 10 kbps

2: 20 kbps

3: 50 kbps

4: 125 kbps

5: 250 kbps

6: 500 kbps

7: 800 kbps

8: 1 Mbps

Default: 6

Range: 0 to 8

F6-40

(03D5)

CompoNet Node

Address

CN Node Adress

Reserved.

F6-41

(03D6)

CompoNet

Communication Speed

CN Baud Rate

Reserved.

F6-45

(02FB) BACnet Node Address BAC Node Address

Sets BACnet physical node address.

Default: 1

Min.: 0

Max.: 127

F6-46

(02FC) BACnet Baud Rate

BAC Baud Rate

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19.2 kbps

5: 38.4 kbps

6: 57.6 kbps

7: 76.8 kbps

8: 115.2 kbps

0: 1200

1: 2400

2: 4800

3: 9600

4: 19200

5: 38400

6: 57600

7: 76800

8: 115200

Default: 3

Range: 0 to 8

F6-47

(02FD) Rx to Tx Wait Time

Rx to Tx Wait T

Sets the wait time between receiving and sending for BACnet. Default: 5 ms

Min.: 5

Max.: 65

F6-48

(02FE)

BACnet Device Object

Identifier 0

BAC Dev Obj Id 0

Sets the least significant word for BACnet.

Default: 0

Min.: 0

Max.: FFFF

F6-49

(02FF)

BACnet Device Object

Identifier 1

BAC Dev Obj Id 1

Sets the most significant word for BACnet.

Default: 0

Min.: 0

Max.: 3F

F6-50

(03C1)

DeviceNet MAC

Address

DN MAC Address

Selects the drive MAC address.

Default: 64

Min.: 0

Max.: 64

F6-51

(03C2)

DeviceNet

Communication Speed

DN Baud Rate

0: 125 kbps

1: 250 kbps

2: 500 kbps

3: Set from Network

4: Auto Detect

0: 125 kbps

1: 250 kbps

2: 500 kbps

3: Adjustable from network

4: Detect automatically

Default: 4

Range: 0 to 4

B.6 F: Options

298

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide