B.3 C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier frequency

selections.

u

C1: Acceleration and Deceleration Times

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C1-01

(0200)

Acceleration Time 1

Accel Time 1

Sets the time to accelerate from 0 to maximum frequency.

Default: 10.0 s

Min.: 0.0
Max.: 6000.0

<1>

166

C1-02

(0201)

Deceleration Time 1

Decel Time 1

Sets the time to decelerate from maximum frequency to 0.

166

C1-03

(0202)

Acceleration Time 2

Accel Time 2

Sets the time to accelerate from 0 to maximum frequency.

Default: 10.0 s

Min.: 0.0
Max.: 6000.0

<1>

166

C1-04

(0203)

Deceleration Time 2

Decel Time 2

Sets the time to decelerate from maximum frequency to 0.

166

C1-05

(0204)

Acceleration Time 3

(Motor 2 Accel Time 1) Accel Time 3

Sets the time to accelerate from 0 to maximum frequency.

Default: 10.0 s

Min.: 0.0
Max.: 6000.0

<1>

166

C1-06

(0205)

Deceleration Time 3

(Motor 2 Decel Time 1) Decel Time 3

Sets the time to decelerate from maximum frequency to 0.

166

C1-07

(0206)

Acceleration Time 4

(Motor 2 Accel Time 2) Accel Time 4

Sets the time to accelerate from 0 to maximum frequency.

Default: 10.0 s

Min.: 0.0
Max.: 6000.0

<1>

166

C1-08

(0207)

Deceleration Time 4

(Motor 2 Decel Time 2) Decel Time 4

Sets the time to decelerate from maximum frequency to 0.

166

C1-09

(0208)

Fast Stop Time

Fast Stop Time

Sets the time for the Fast Stop function.

Note:

Parameter setting cannot be changed when the

drive is operating the motor in models 4A0930

and 4A1200.

Default: 10.0 s

Min.: 0.0
Max.: 6000.0

<1>

C1-10

(0209)

Accel/Decel Time

Setting Units

Acc/Dec Units

0: 0.01 Seconds

1: 0.1 Seconds

0: 0.01 s (0.00 to 600.00 s)

1: 0.1 s (0.0 to 6000.0 s)

Default: 1

Range: 0, 1

C1-11

(020A)

Accel/Decel Time

Switching Frequency

Acc/Dec SW Freq

Sets the frequency to switch between accel/decel time settings Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

<1> Setting range value is determined by parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range

becomes 0.00 to 600.00 seconds.

B.3 C: Tuning

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

275