A.3 drive specifications – Yaskawa CIMR-AU 200V Drives User Manual

Page 259

Advertising
background image

Item

Specification

Protection

Functions

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when output current exceeds 200% of Heavy Duty Rating

Overload Protection

Drive stops after 60 s at 150% of rated Heavy Duty output current

<6>

Overvoltage Protection

200 V class: Stops when DC bus voltage exceeds approx. 410 V

400 V class: Stops when DC bus voltage exceeds approx. 820 V

600 V class: Stops when DC bus voltage exceeds approx. 1040 V

Undervoltage Protection

200 V class: Stops when DC bus voltage falls below approx. 190 V

400 V class: Stops when DC bus voltage falls below approx. 380 V

600 V class: Stops when DC bus voltage falls below approx. 475 V

Momentary Power Loss

Ride-Thru

Immediately stop after 15 ms or longer power loss

<7>

.

Continuous operation during power loss than 2 s (standard)

<8>

Heatsink Overheat Protection Thermistor

Braking Resistor Overheat

Protection

Overheat input signal for braking resistor (Optional ERF-type, 3% ED)

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<9>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F), IP00 enclosure: -10 °C to +50 °C

(14 °F to 122 °F)

Humidity

95 RH% or less (no condensation)

Storage Temperature

-20 °C to +60 °C (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Vibration/Shock

10 to 20 Hz: 9.8 m/s

2

<10>

20 to 55 Hz: 5.9 m/s

2

(2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0099)

2.0 m/s

2

(2A0250 to 2A0415, 4A0208 to 4A1200, and 5A0125 to 5A0242)

Standard

• UL508C
• IEC/EN 61800-3, IEC/EN 61800-5-1
• Two Safe Disable inputs and one EDM output according to ISO/EN 13849-1 Cat. 3 PLd, IEC/EN

61508 SIL2

• CSA

<11>

Protection Design

IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure

<12>

<1> Select control modes in accordance with drive capacity.
<2> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<3> Disable Stall Prevention during deceleration (L3-04 = 0) when using a regenerative converter, a regenerative unit, a braking resistor or the Braking

Resistor Unit. The default setting for the Stall Prevention function will interfere with the braking resistor.

<4> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed

down to zero in the shortest time.

<5> Actual specifications may vary depending on motor characteristics.
<6> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<7> May be shorter due to load conditions and motor speed.
<8> A separate Momentary Power Loss Ride-Thru Unit is required for models 2A0004 to 2A0056 and 4A0002 to 4A0031 if the application needs to

continue running for up to 2 seconds during a momentary power loss.

<9> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<10> Models 4A0930 and 4A1200 are rated at 5.9 m/s

2

.

<11> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to Insulation coordination: class

1.

<12> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while

maintaining IP20 conformity. This is applicable to models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242.