Terminal am/fm signal selection, Terminal dm+ and dm- output signal selection, Refer to terminal – Yaskawa CIMR-AU 200V Drives User Manual

Page 138: 8 control i/o connections

Advertising
background image

u

Terminal AM/FM Signal Selection

The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board

as explained in

Table 3.17

. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.

The default selection is voltage output for both terminals.

Table 3.17 Jumper S5 Settings

Terminal

Voltage Output

Current Output

Terminal AM

AM

FM

V

I

AM

FM

V

I

Terminal FM

AM

FM

V

I

AM

FM

V

I

Table 3.18 Parameter H4-07 and H4-08 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H4-07

Terminal AM signal level selection

0: 0 to 10 Vdc

1: -10 to 10 Vdc

2: 4 to 20 mA

0 to 2

0

H4-08

Terminal FM signal level selection

u

Terminal DM+ and DM- Output Signal Selection

Slide switch S6 selects N.C. or N.O. as the state of the DM+ and DM- terminals for EDM output. The switch is initially set

to N.C. Slide switch S6 is available on terminal board ETC74030o.

Table 3.19 EDM Switch Settings

S2 Position

Description

N.O.

Normally open

N.C.

Normally closed (default setting)

Note:

Refer to Safe Disable Input Function on page 368

for details on EDM.

3.8 Control I/O Connections

138

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

Advertising