6.2 Periodic Maintenance

The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance warning

and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to check predicted

maintenance periods for the components listed below.
• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
• IGBTs
For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.

u

Replacement Parts

Table 6.3

contains the estimated performance life of components that require replacement during the life of the drive. Only

use Yaskawa replacement parts for the appropriate drive model and revision.

Table 6.3 Estimated Performance Life

Component

Estimated Performance Life

Cooling Fan, Circulation Fan

10 years

Electrolytic Capacitors

10 years

<1>

<1> Electrolytic capacitors cannot be replaced on some lower capacity models. Complete drive replacement may be required for these models.

NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing parts

to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use.

Usage conditions for estimated performance life:

Ambient temperature: Yearly average of 40 °C (IP00/Open Type enclosure)

Load factor: 80% maximum

Operation time: 24 hours a day

n

Performance Life Monitors Maintenance Monitors

The drive calculates the maintenance period for components that may require replacement during the life of the drive. A

percentage of the maintenance period is displayed on the digital operator by viewing the appropriate monitor parameter.
When the maintenance period reaches 100%, there is increased risk that the drive may malfunction. Yaskawa recommends

checking the maintenance period regularly to ensure maximum performance life.

Refer to Recommended Periodic Inspection on page 229

for more details.

Table 6.4 Performance Life Monitors Used for Component Replacement

Parameter

Component

Contents

U4-03

Cooling Fan

Circulation Fan

Control Board Cooling

Fan

Displays the accumulated operation time of the fan from 0 to 99999 hours. This value is automatically reset to

0 after it reaches 99999.

U4-04

Displays the accumulated fan operation time as a percentage of the specified maintenance period.

U4-05

DC Bus Capacitors

Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.

U4-06

Pre-charge Circuit

Displays the number of times the drive is powered up as a percentage of the performance life of the inrush

circuit.

U4-07

IGBT

Displays the percentage of the maintenance period reached by the IGBTs.

6.2 Periodic Maintenance

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

231