Using the pulse train output, 8 control i/o connections – Yaskawa CIMR-AU 200V Drives User Manual

Page 136

Advertising
background image

u

Sinking/Sourcing Mode Selection for Safe Disable Inputs

Note:

Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,

ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.

Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe Disable

inputs H1 and H2 as shown in

Table 3.13

(Default: Source mode, internal power supply).

Table 3.13 Safe Disable Input Sink/Source/External Power Supply Selection

Mode

Drive Internal Power Supply

External 24 Vdc Power Supply

Sinking Mode

24 Vdc

H1

H2

HC

Jumper S3

24 Vdc

H1

H2

HC

External

24 Vdc

Jumper S3

Sourcing Mode

24 Vdc

H1

H2

HC

Jumper S3

24 Vdc

H1

H2

HC

External

24 Vdc

Jumper S3

u

Using the Pulse Train Output

The pulse train output terminal MP can supply power or be used with an external power supply.

NOTICE: Connect peripheral devices in accordance with the specifications. Failure to comply may cause unexpected drive operation, and

can damage the drive or connected circuits.

n

Using Power from the Pulse Output Terminal (Source Mode)

The high voltage level of the pulse output terminal depends on the load impedance.

Load Impedance R

L

(kΩ)

Output Voltage V

MP

(V) (insulated)

1.5 kΩ

5 V

4 kΩ

8 V

10 kΩ

10 V

Note:

The load resistance needed in order to get a certain high level voltage V

MP

can be calculated by: R

L

= V

MP

• 2 / (12 – V

MP

)

MP

AC

V

MP

R

L

Load Impedance

Figure 3.32 Pulse Output Connection Using Internal Voltage Supply

3.8 Control I/O Connections

136

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide