B.1 a: initialization parameters, A1: initialization – Yaskawa CIMR-AU 200V Drives User Manual

Page 264

Advertising
background image

B.1 A: Initialization Parameters

Table B.1 Symbols and Icons Used in Parameter Descriptions

Symbol

Description

Parameter can be changed during run.

Motor 2

Refers to a second motor when the drive is operating two motors. Use multi-function input terminals to switch

between motors.

The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor

Control Method, Password, User Parameters and more.

u

A1: Initialization

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

A1-00

(0100)

<1>

Language Selection

Select Language

0: English

1:

(Japanese)

2: Deutsch

3: Fran

çais

4: Italiano

5: Español

6: Portuguêse

7:

8: Czech

9: Russian

10: Turkish

11: Polish

12: Greek

0: English

1: Japanese

2: German

3: French

4: Italian

5: Spanish

6: Portuguese

7: Chinese

8: Czech

9: Russian

10: Turkish

11: Polish

12: Greek

Note:

Settings 8 to 12 can only be selected from an LCD

operator with version REV: F or later. The

version is listed on the back of the operator.

Default: 0
Range: 0 to 12

<2>

A1-01

(0101)

<3>

Access Level Selection

Access Level

0: Operation Only

1: User Parameters

2: Advanced Level

0: View and set A1-01 and A1-04. Uo-oo parameters can also

be viewed.

1: User Parameters (access to a set of parameters selected by the

user, A2-01 to A2-32)

2: Advanced Access (access to view and set all parameters)

Default: 2

Range: 0 to 2

A1-02

(0102)

<1>

Control Method

Selection

Control Method

0: V/f Control

1: V/f with PG

2: Open Loop Vector

3: Closed Loop Vect

5: PM OpenLoop Vect

6: PM

AdvOpLoopVect

7: PM ClosedLoopVct

0: V/f Control

1: V/f Control with PG

2: Open Loop Vector Control

3: Closed Loop Vector Control

5: Open Loop Vector Control for PM

6: Advanced Open Loop Vector Control for PM

7: Closed Loop Vector Control for PM

Default: 2

Range: 0 to 3;

5 to7

158

A1-03

(0103)

Initialize Parameters

Init Parameters

0: No Initialize

1110: User Initialize

2220: 2-Wire Initial

3330: 3-Wire Initial

5550: Term->Cntrl Int

0: No initialization

1110: User Initialize (parameter values must be stored using

parameter o2-03)

2220: 2-Wire initialization

3330: 3-Wire initialization

5550: oPE04 error reset

Default: 0

Range: 0 to

3330;

5550

158

A1-04

(0104)

Password

Enter Password

When the value set into A1-04 does not match the value set into

A1-05, parameters A1-01 through A1-03, A1-06, A1-07, and

A2-01 through A2-32 cannot be changed.

Default: 0000

Min.: 0000

Max.: 9999

A1-05

(0105)

Password Setting

Select Password

When the value set into A1-04 does not match the value set into

A1-05, parameters A1-01 through A1-03, A1-06, A1-07, and

A2-01 through A2-32 cannot be changed.

Default: 0000

Min.: 0000

Max.: 9999

A1-06

(0127)

Application Preset

Application Sel

0: General

1: Pump

2: Conveyor

3: Exhaust Fan

4: Supply Fan

5: Compressor

0: General-purpose

1: Water supply pump

2: Conveyor

3: Exhaust fan

4: HVAC fan

5: Air compressor

Default: 0

Range: 0 to 5

A1-07

(0128)

DriveWorksEZ

Function Selection

DWEZ Func Sel

0: Disabled

1: Enabled

2: Terminal Control

0: DWEZ Disabled

1: DWEZ Enabled

2: Digital input (enabled when H1-oo = 9F)

Default: 0

Range: 0 to 2

B.1 A: Initialization Parameters

264

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

Advertising