Yaskawa CIMR-AU 200V Drives User Manual

Page 304

Advertising
background image

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

20 to 2F External fault

20: NO/Always Det,

Ramp to Stop

21: NC/Always Det,

Ramp to Stop

22: NO/During RUN,

Ramp to Stop

23: NC/During RUN,

ramp to stop

24: NO/ Always Det,

Coast to Stop

25: NC/Always Det,

Coast to Stop

26: NO/During RUN,

Coast to Stop

27: NC/During RUN,

Coast to Stop

28: NO/Always Det,

Fast-Stop

29: NC/Always Det,

Fast-Stop

2A: NO/During RUN,

Fast-Stop

2B: NC/During RUN,

Fast- Stop

2C: NO/Always Det,

Alarm Only

2D: NC/Always Det,

Alarm Only

2E: NO/ During RUN,

Alarm Only

2F: NC/During RUN,

Alarm Only

20: N.O., Always detected, ramp to stop

21: N.C., Always detected, ramp to stop

22: N.O., During run, ramp to stop

23: N.C., During run, ramp to stop

24: N.O., Always detected, coast to stop

25: N.C., Always detected, coast to stop

26: N.O., During run, coast to stop

27: N.C., During run, coast to stop

28: N.O., Always detected, Fast Stop

29: N.C., Always detected, Fast Stop

2A: N.O., During run, Fast Stop

2B: N.C., During run, Fast Stop

2C: N.O., Always detected, alarm only (continue running)

2D: N.C., Always detected, alarm only (continue running)

2E: N.O., During run, alarm only (continue running)

2F: N.C., During run, alarm only (continue running)

30

PID integral reset

PID Intgrl Reset

Closed: Resets the PID control integral value.

31

PID integral hold

PID Intgrl Hold

Open: Performs integral operation.

Closed: Maintains the current PID control integral value.

32

Multi-Step Speed

Reference 4

Multi-Step Ref 4

Used in combination with input terminals set to Multi-Step Speed Reference 1, 2,

and 3. Use parameters d1-09 to d1-16 to set reference values.

34

PID soft starter cancel

PID SFS Cancel

Open: PID soft starter is enabled.

Closed: Disables the PID soft starter b5-17.

35

PID input level selection PID Input Invert

Closed: Inverts the PID input signal.

40

Forward run command

(2-Wire sequence)

FwdRun 2Wire Seq

Open: Stop

Closed: Forward run

Note:

Cannot be set together with settings 42 or 43.

41

Reverse run command

(2-Wire sequence)

RevRun 2WireSeq

Open: Stop

Closed: Reverse run

Note:

Cannot be set together with settings 42 or 43.

42

Run command

(2-Wire sequence 2)

Run/Stp 2WireSeq

Open: Stop

Closed: Run

Note:

Cannot be set together with settings 40 or 41.

43

FWD/REV command

(2-Wire sequence 2)

FWD/REV 2WireSeq

Open: Forward

Closed: Reverse

Note:

Determines motor direction, but does not issue a Run command.

Cannot be set together with settings 40 or 41.

44

Offset frequency 1

Offset Freq 1

Closed: Adds d7-01 to the frequency reference.

45

Offset frequency 2

Offset Freq 2

Closed: Adds d7-02 to the frequency reference.

46

Offset frequency 3

Offset Freq 3

Closed: Adds d7-03 to the frequency reference.

47

Node setup

CanOpenNID Setup

Closed: Node setup for SI-S3 enabled.

60

DC Injection Braking

command

DCInj Activate

Closed: Triggers DC Injection Braking.

61

External Speed Search

command 1

Speed Search 1

Closed: Activates Current Detection Speed Search from the maximum output

frequency (E1-04).

B.7 H Parameters: Multi-Function Terminals

304

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

Advertising