L3: stall prevention – Yaskawa CIMR-AU 200V Drives User Manual

Page 315

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L2-06

(048A)

KEB Deceleration

Time

KEB Decel Time

Sets the time required to decelerate from the speed when KEB

was activated to zero speed.

Default: 0.00 s

Min.: 0.00
Max.: 6000.0

<4>

L2-07

(048B)

KEB Acceleration

Time

KEB Accel Time

Sets the time to accelerate to the frequency reference when

momentary power loss is over. If set to 0.0, the active acceleration

time (C1-01, C1-03, C1-05, or C1-07) is used.

Default: 0.00 s

Min.: 0.00
Max.: 6000.0

<4>

L2-08

(048C)

Frequency Gain at KEB

Start

KEB Freq Red

Sets the percentage of output frequency reduction at the

beginning of deceleration when the KEB Ride-Thru function is

started.

Reduction = (slip frequency before KEB) × (L2-08/100) × 2

Default: 100%

Min.: 0

Max.: 300

L2-10

(048E)

KEB Detection Time

(Minimum KEB Time) KEB Detect Time

Sets the time to perform KEB Ride-Thru.

Default: 50 ms

Min.: 0

Max.: 2000

L2-11

(0461)

DC Bus Voltage

Setpoint during KEB

KEB DC Bus Level

Sets the desired value of the DC bus voltage during KEB Ride-

Thru.

Default:

<2>

Min.: 150 Vdc
Max.: 400 Vdc

<5>

L2-29

(0475) KEB Method Selection

KEB Mode Sel

0: Single Mode KEB1

1: Single Mode KEB2

2: System Mode

KEB1

3: System Mode

KEB2

0: Single Drive KEB Ride-Thru 1

1: Single Drive KEB Ride-Thru 2

2: System KEB Ride-Thru 1

3: System KEB Ride-Thru 2

Default: 0

Range: 0 to 3

<1> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Default setting is determined by parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range

becomes 0.00 to 600.00 seconds.

<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but

set the value below 1040 Vdc (overvoltage protection level).

u

L3: Stall Prevention

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L3-01

(048F)

Stall Prevention

Selection during

Acceleration

StallP Accel Sel

0: Disabled

1: General Purpose

2: Intelligent

0: Disabled.

1: General purpose. Acceleration is paused as long as the current

is above the L3-02 setting.

2: Intelligent. Accelerate in the shortest possible time without

exceeding the L3-02 level.

Note:

Setting 2 is not available when using OLV/PM.

Default: 1

Range: 0 to 2

182

L3-02

(0490)

Stall Prevention Level

during Acceleration

StallP Accel Lvl

Used when L3-01 = 1 or 2. 100% is equal to the drive rated

current.

Default:

<1>

Min.: 0%
Max.: 150%

<1>

183

L3-03

(0491)

Stall Prevention Limit

during Acceleration

StallPAcc LowLim

Sets Stall Prevention lower limit during acceleration when

operating in the constant power range. Set as a percentage of drive

rated current.

Default: 50%

Min.: 0

Max.: 100

184

B.8 L: Protection Function

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

315