Flange type heat loss data, Flange type terminal and wiring specifications – Yaskawa CIMR-AU 200V Drives User Manual

Page 75

Advertising
background image

n

Flange Type Heat Loss Data

Table 2.20 Models 4o0088 and 4o0103

Drive Model

Voltage

Class

Input Type

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

4A0088

400

6-Pulse

308

684

992

254

563

817

39 (85.8)

4A0103

357

848

1205

299

723

1022

39 (85.8)

4T0088

<1>

12-Pulse

285

669

954

241

556

797

35 (77.0)

4T0103

<1>

329

827

1156

285

714

999

35 (77.0)

<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.

n

Flange Type Terminal and Wiring Specifications

Wire gauges and tightening torques
are identical to standard models.

(2) GROUND
TERMINALS

CONTROL CIRCUIT
TERMINALS

MAIN CIRCUIT
TERMINALS

SECTION A-A

Unit: in. [mm]

Figure 2.37 Models 4A0088 and 4A0103

2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

75

2

Mechanical Installation

Advertising