No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-32

(04E2)

Cooling Fan Failure

Selection

MC/FAN PS FltSel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

4: Run@L8-19 Rate

Determines drive response when a fault occurs with the internal

cooling fan.

0: Ramp to stop

1: Coast to stop

2: Fast stop (Decelerate to stop using the deceleration time set to

C1-09)

3: Alarm only (“FAn” will flash)

4: Continue operation at reduced speed as set to L8-19.

Default: 1

Range: 0 to 4

L8-35

(04EC)

Installation Method

Selection

Installation Sel

0: IP00/OpenChassis

2: IP20/Nema Type 1

3: Finless/Fin Ext

0: IP00/Open-Chassis enclosure

1: Side-by-Side mounting

2: IP20/NEMA Type 1 enclosure

3: Finless model drive or external heatsink installation

Default:

<3>

Range: 0 to 3

L8-38

(04EF)

Carrier Frequency

Reduction

Fc Reduct dur OL

0: Disabled

1: Active below 6Hz

2: Active @ any Spd

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default:

<4>

Range: 0 to 2

L8-40

(04F1)

Carrier Frequency

Reduction Off Delay

Time

Fc Reduct Time

Sets the time that the drive continues running with reduced carrier

frequency after the carrier reduction condition is gone. Setting

0.00 s disables the carrier frequency reduction time.

Default:

<5>

Min.: 0.00 s

Max.: 2.00 s

L8-41

(04F2)

High Current Alarm

Selection

High Cur Alm Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled. An alarm is triggered at output currents above 150%

of drive rated current.

Default: 0

Range: 0, 1

L8-55

(045F)

Internal Braking

Transistor Protection

DB Tr protection

0: Disable

1: Enable

0: Disabled. Disable when using a regen converter or optional

braking unit.

1: Protection enabled.

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 1

Range: 0, 1

L8-78

(02CC)

Power Unit Output

Phase Loss Protection

LF3 Det Sel

0: Disabled

1: Enabled

Enables motor protection in the event of output phase loss.

0: Disabled

1: Enabled

Note:

This parameter is only available in models 4A0930

and 4A1200.

Default: 1

Range: 0, 1

L8-93

(073C)

LSo Detection Time at

Low Speed

LSO Det Time

Sets the amount of time until baseblock is executed after detecting

pull-out at low speed.

Default: 1.0 s

Min.: 0.0

Max.: 10.0

L8-94

(073D)

LSo Detection Level at

Low Speed

LSO Det Level

Determines the detection level of pull-out at low speed.

Default: 3%

Min.: 0

Max.: 10

L8-95

(073F)

Average LSo Frequency

at Low Speed

Num of LSO Avg

Sets the average number of times pull-out can occur at low speed.

Default: 10

times

Min.: 1

Max.: 50

<1> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> The setting range is 0.0 to 300.0% for models 4A0930 and 4A1200.
<3> Default setting is determined by parameter o2-04, Drive Model Selection.
<4> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<5> Default setting is determined by parameter A1-02, Control Method Selection.

B.8 L: Protection Function

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide