No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H2-06

(0437)

Watt Hour Output Unit

Selection

Pwr Mon Unit Sel

Sets the output units for the watt hours when Watt Hour Pulse

Output is selected as the digital output (H2-01, H2-02, or H2-03

= 39).

Outputs a 200 ms pulse signal when the watt hour counter

increases by the units selected.

0: 0.1 kWh units

1: 1 kWh units

2: 10 kWh units

3: 100 kWh units

4: 1000 kWh units

Default: 0

Range: 0 to 4

H2-07

(0B3A)

<1>

MEMOBUS Register 1

Address Select

MFDO Regs1 Addr

Sets the addresses of the MEMOBUS/Modbus registers from

which data will be sent to contact outputs 62 and 162.

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 1

Range: 1 to 1FFF

H2-08

(0B3B)

<1>

MEMOBUS Register 1

Bit Select

MFDO Regs1 Bit

Sets the bits for the MEMOBUS/Modbus registers from which

data will be sent to contact outputs 62 and 162.

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 0

Range: 0 to FFFF

H2-09

(0B3C)

<1>

MEMOBUS Register 2

Address Select

MFDO Regs2 Addr

Sets the addresses of the MEMOBUS/Modbus registers from

which data will be sent to contact outputs 63 and 163.

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 1

Range: 1 to 1FFF

H2-10

(0B3D)

<1>

MEMOBUS Register 2

Bit Select

MFDO Regs2 Bit

Sets the bits for the MEMOBUS/Modbus registers from which

data will be sent to contact outputs 63 and 163.

Note:

This parameter is not available in models

4A0930 and 4A1200.

Default: 0

Range: 0 to FFFF

<1> Available in drive software versions PRG: 1019 and later.

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

0

During run

During RUN 1

Closed: A Run command is active or voltage is output.

1

Zero speed

Zero Speed

Open: Output speed is greater than the value of E1-09 (Minimum Output

Frequency) or b2-01 (DC Injection Braking Start Frequency).

Closed: Output frequency is less than or equal to the value of E1-09 (Minimum

Output Frequency) or b2-01 (DC Injection Braking Start Frequency).

2

Speed agree 1

Fref/Fout Agree1

Closed: Output frequency equals the speed reference (plus or minus the hysteresis

set to L4-02).

177

3

User-set speed agree 1

Fref/Set Agree 1

Closed: Output frequency and speed reference equal L4-01 (plus or minus the

hysteresis set to L4-02).

178

4

Frequency detection 1

Freq Detect 1

Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis

determined by L4-02.

5

Frequency detection 2

Freq Detect 2

Closed: Output frequency is greater than or equal to the value in L4-01 with

hysteresis determined by L4-02.

6

Drive ready

Drive Ready

Closed: Power up is complete and the drive is ready to accept a Run command.

7

DC bus undervoltage

DC Bus Undervolt

Closed: DC bus voltage is below the Uv trip level set in L2-05.

8

During baseblock

(N.O.)

BaseBlk 1

Closed: Drive has entered the baseblock state (no output voltage).

9

Frequency reference

source

Ref Source

Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or

b1-15).

Closed: Digital operator supplies the frequency reference.

A

Run command source

Run Cmd Source

Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).

Closed: Digital operator supplies the Run command.

B

Torque detection 1

(N.O.)

Trq Det 1 N.O.

Closed: An overtorque or undertorque situation has been detected.

C

Frequency reference

loss

Loss of Ref

Closed: Analog frequency reference has been lost.

Frequency reference loss is detected when the frequency reference drops below

10% of the reference within 400 ms.

D

Braking resistor fault

DB Overheat

Closed: Braking resistor or transistor is overheated or faulted out.

Note:

This setting is not available in models 4A0930 and 4A1200.

B.7 H Parameters: Multi-Function Terminals

306

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide