Yaskawa CIMR-AU 200V Drives User Manual

Page 234

Advertising
background image

Figure 6.3 Remove the Terminal Board

Figure 6.4 Disconnected Removable Terminal Board

4.

Disconnect all option cards and options, making sure they are intact before reusing.

5.

Replace the drive and wire the main circuit.

n

Installing the Drive

1.

After wiring the main circuit, connect the terminal block to the drive as shown in

Figure 6.5

. Use the installation screw

to fasten the terminal block into place.

Figure 6.5 Install the Terminal Board

2.

Reconnect options for the new drive the same way the options were connected in the old drive. Connect option boards

to the same option ports in the new drive that were used in the old drive.

3.

Replace the terminal cover.

4.

After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If an

oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting parameter

A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through o4-12 to 0, and

parameter o4-13 to 1.

6.3 Drive Replacement

234

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide