Table 4.29, Auto-tuning for permanent magnet motors – Yaskawa CIMR-AU 200V Drives User Manual

Page 188

Advertising
background image

Table 4.29 Auto-Tuning Input Data

Input Value

Input

Parameter

Unit

Tuning Type (T1-01)

0

Standard

1

Stationary 1

2

Line-to-Line

Resistance

3

Rotational for

V/f Control

4

Stationary 2

5

Stationary 3

Control Mode

A1-02

2, 3

2, 3

0, 1, 2, 3

0, 1

2, 3

2, 3

Motor rated power

T1-02

kW

YES

YES

YES

YES

YES

YES

Motor rated voltage

T1-03

Vac

YES

YES

YES

YES

YES

Motor rated current

T1-04

A

YES

YES

YES

YES

YES

YES

Motor rated frequency

T1-05

Hz

YES

YES

YES

YES

YES

Number of motor poles

T1-06

-

YES

YES

YES

YES

YES

Motor rated Speed

T1-07

r/min

YES

YES

YES

YES

YES

PG Number of pulses per

revolution

T1-08

-

YES

<1>

YES

<1>

YES

<1>

YES

<1>

Motor no-load current

T1-09

A

YES

<2>

YES

YES

Motor rated Slip

T1-10

Hz

YES

YES

Motor iron loss

T1-11

W

YES

YES

<1> Input data is needed for CLV/PM only.
<2> Motor no-load current is required. If the no-load current is not shown on the motor nameplate, use the default value. The default value is set for

Yaskawa standard motors.

n

Auto-Tuning for Permanent Magnet Motors

Automatically sets the V/f pattern and motor parameters E1-oo and E5-oo when a PM motor is used. Additionally, the

feature also sets some F1-oo parameters for speed feedback detection in Closed Loop Vector.

Table 4.30 Types of Auto-Tuning for Permanent Magnet Motors

Type

Setting

Application Conditions and Benefits

Control Mode

OLV/PM

AOLV/PM

CLV/PM

PM Motor Parameter

Settings

T2-01 = 0

• Motor does not rotate during Auto-Tuning.
Motor test report or motor data similar to

Table 4.31

are

available.

YES

YES

YES

PM Stationary Auto-

Tuning

T2-01 = 1

• A motor test report listing motor data is not available.
• Drive automatically calculates and sets motor parameters.

YES

YES

YES

PM Stationary Auto-

Tuning for Stator

Resistance

T2-01 = 2

• Useful to tune the drive when the motor data were set up

manually or by motor code and the cable is longer than 50

m.

• Should also be performed if the cable length has changed

after prior tuning.

YES

YES

YES

Z Pulse Offset Tuning

T2-01 = 3

• PG encoder has been replaced. Calculates the Z Pulse offset.
• Requires the motor to rotate with no load or very low load.

YES

Back EMF Constant

Tuning

T2-01 = 11

• Use when a motor test is not available.
• Tunes the motor induction voltage only.
• Should be performed after motor data are set and the encoder

offset is adjusted.

• The motor must be uncoupled from the mechanical system

(remove loads).

YES

High Frequency

Injection Parameter

Tuning

T2-01 = 13

• The motor rotated in reverse or STo fault (Motor Step-Out)

occurred at startup in OLV/PM.

• Low speed and no torque after activating the high frequency

injection control (n8-57 = 1) in AOLV/PM.

• Faults, such as the motor rotating in reverse, occurred when

the power was turned on during initial startup in CLV/PM.

YES

YES

PM Rotational Auto-

Tuning

T2-01 = 14

• A motor test report listing motor data is not available.
• Motor can be decoupled from the load and rotate freely while

Auto-Tuning is performed. Drive automatically calculates

and sets motor parameters.

• PM Rotational Auto-Tuning gives more accurate results than

Stationary Auto-Tuning.

YES

YES

YES

4.7 Auto-Tuning

188

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide