L3-02: stall prevention level during acceleration – Yaskawa CIMR-AU 200V Drives User Manual

Page 183

Advertising
background image

Stall Prevention Level
During Acceleration

L3-02

L3-02

-15%

Output current

Output frequency

Time

Time

Controls the output frequency
to prevent the motor from stalling

Figure 4.33 Stall Prevention During Acceleration for Induction Motors

• Open Loop Vector Control for PM:

Acceleration stops when the output current reaches the level set to parameter L3-02. When the time set to parameter L3-27

passes, the drive decelerates using the deceleration time set to L3-22. Deceleration stops when the current falls below 85%

of L3-02,. The drive will attempt to reaccelerate after the time set to L3-27.

Output current

L3-02

Output frequency

Time

Time

Deceleration

using L3-22

L3-27

L3-27

15 % of L3-02

Figure 4.34 Stall Prevention During Acceleration for Permanent Magnet Motors

Setting 2: Intelligent Stall Prevention

The drive disregards the selected acceleration time and attempts to accelerate in the minimum time. The acceleration rate is

adjusted so the current does not exceed the value set to parameter L3-02.

n

L3-02: Stall Prevention Level during Acceleration

Sets the output current level at which the Stall Prevention during acceleration is activated.

No.

Name

Setting Range

Default

L3-02

Stall Prevention Level during Acceleration

0 to 150%

<1>

<1>

<1> The upper limit and default value is determined by the duty rating and the carrier frequency derating selection (C6-01 and L8-38 respectively).

• Lower L3-02 if stalling occurs when using a motor that is relatively small compared to the drive.
• Also set parameter L3-03 when operating the motor in the constant power range.

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

183

4

Start-Up Programming & Operation