Flange Type Heat Loss Data

Table 2.26 Models 2A0360 and 2A0415, 4o0250 to 4o0362, and 5A0192 and 5A0242

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc =

<1>

)

Internal

External

Total

Internal

External

Total

2A0360

200

894

2698

3592

783

2564

3347

108 (238)

2A0415

954

2672

3626

954

2672

3626

<1> Carrier frequency is set to 5 kHz in model 2A0360 and set to 2 kHz in model 2A0415.

Drive Model

Voltage

Class

Input Type

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc =

<1>

)

Internal

External

Total

Internal

External

Total

4A0250

400

6-Pulse

803

2379

3182

715

2360

3075

106 (233)

4A0296

905

2448

3353

787

2391

3178

112 (246)

4A0362

1130

3168

4298

985

3075

4060

117 (257)

4T0250

<2>

12-Pulse

729

2305

3034

663

2308

2971

90 (198)

4T0296

<2>

772

2308

3080

694

2295

2989

95 (209)

4T0362

<2>

874

3168

4042

788

3075

3863

97 (214)

<1> Carrier frequency is set to 5 kHz in models 4o0250, 4o0296, and 4T0362 and set to 2 kHz in model 4A0362.
<2> Refer to manual TOEP C710616 50 for information on 12-pulse models.

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 2 kHz)

Internal

External

Total

Internal

External

Total

5A0192

600

769

2420

3189

648

2114

2762

117 (257)

5A0242

1131

3100

4231

896

2526

3422

117 (257)