Yaskawa CIMR-AU 200V Drives User Manual
Page 93
DETAIL A
Unit: in. [mm]
SECTION B-B
DETAIL A
CONTROL
CIRCUIT
TERMINALS
MAIN CIRCUIT
TERMINALS
(2) GROUND
TERMINALS
Figure 2.52 Models 4T0250 to 4T0362
Table 2.27 12-Pulse Models 4T0250, 4T0296, and 4T0362 Terminal and Wire Specifications for Main Circuit and Ground
Drive Model
Terminal
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4T0250
<1>
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
⊖, ⊕3
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0
(22.1 to 26.6)
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
4T0296
<1>
4T0362
<1>
R/L1, S/L2, T/L3
Refer to applicable codes for wire size
M10
18 to 23
(159.3 to 203.6)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
M12
32 to 40
(283.2 to 354.0)
⊖, ⊕3
22 to 1/0 (0.3 to 53.5)
M6
2.5 to 3.0
(22.1 to 26.6)
Refer to applicable codes for wire size
M12
32 to 40
(283.2 to 354.0)
<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.
2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide
93
2
Mechanical Installation