4.4 Powering Up the Drive

u

Powering Up the Drive and Operation Status Display

n

Powering Up the Drive

Review the following checklist before turning the power on.

Item to Check

Description

Power supply voltage

200 V class: Three-phase 200 to 240 Vac 50/60 Hz

400 V class: Three-phase 380 to 480 Vac 50/60 Hz

600 V class: Three-phase 500 to 600 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
Check for proper grounding of drive and motor.

Drive output terminals and

motor terminals

Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.

Control circuit terminals

Check control circuit terminal connections.

Drive control terminal status

Open all control circuit terminals (off).

Status of the load and connected

machinery

Decouple the motor from the load.

<1> Confirm the following when connecting models CIMR-Ao4A0930 and 4A1200: Remove the jumpers on R1/L11, S1/L21, and T1/L31 when using

12-phase rectification. When operating without 12-phase rectification, properly wire terminals R1/L11, S1/L21, and T1/L31 in addition to terminals
R/L1, S/L2, and T/L3.

n

Status Display

When the power supply to the drive is turned on, the digital operator lights will appear as follows:

Status

Name

Description

Normal

Operation

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALARM

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

The data display area displays the frequency reference.

is lit.

Fault

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALM

- MODE -

EF3

Ext Fault S3

DRV

FWD

RESET

External fault (example)

Data displayed varies by the type of fault.

Refer to Fault Displays, Causes, and Possible

Solutions on page 201

for more information.

and

are lit.

4.4 Powering Up the Drive