B.13 u: monitors, U1: operation status monitors, Refer to u1 – Yaskawa CIMR-AU 200V Drives User Manual

Page 335: U1 - 10

Advertising
background image

B.13 U: Monitors

Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.

u

U1: Operation Status Monitors

No.

(Addr.

Hex)

Name

Description

Analog

Output Level

Unit

U1-01

(0040) Frequency Reference

Frequency Ref

Monitors the frequency reference. Display units are determined

by o1-03.

10 V: Max

frequency

(-10 to +10 V)

0.01 Hz

U1-02

(0041) Output Frequency

Output Freq

Displays the output frequency. Display units are determined by

o1-03.

10 V: Max

frequency

(-10 to +10 V)

0.01 Hz

U1-03

(0042) Output Current

Output Current

Displays the output current.

Note:

The unit is expressed in 1 A for models 4A0930

and 4A1200.

10 V: Drive

rated current

<1> <2>

U1-04

(0043) Control Method

Control Method

0: V/f Control

1: V/f Control with PG

2: Open Loop Vector Control

3: Closed Loop Vector Control

No signal output

available

U1-05

(0044) Motor Speed

Motor Speed

Displays the motor speed feedback. Display units are determined

by o1-03.

10 V: Max

frequency

(-10 to +10 V)

0.01 Hz

U1-06

(0045)

Output Voltage

Reference

Output Voltage

Displays the output voltage.

10 V: 200 Vrms

<3>

0.1 Vac

U1-07

(0046) DC Bus Voltage

DC Bus Voltage

Displays the DC bus voltage.

10 V: 400 V

<3>

1 Vdc

U1-08

(0047) Output Power

Output kWatts

Displays the output power (this value is calculated internally).

10 V: Drive

capacity

(motor capacity)

kW
(-10 to +10 V)

<4>

<4>

U1-09

(0048) Torque Reference

Torque Reference

Monitors the internal torque reference.

10 V: Motor

rated torque

(-10 to +10 V)

0.1%

U1-10

(0049) Input Terminal Status

Input Term Sts

Displays the input terminal status.

U1 - 10=

00000000

Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)

1
1
1
1
1
1
1
1

No signal output

available

B.13 U: Monitors