Flange Type Heat Loss Data

Table 2.16 Models 2A0110 and 4o0058

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

2A0110

200

286

719

1005

211

510

721

23 (50.6)

Drive Model

Voltage

Class

Input Type

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

4A0058

400

6-Pulse

215

471

686

170

349

519

23 (50.6)

4T0058

<1>

12-Pulse

197

453

650

159

341

500

21 (46.2)

<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.

n