Refer to c6-01: drive duty mode, Table 4.9, C6-01: drive duty mode selection – Yaskawa CIMR-AU 200V Drives User Manual

Page 167: 6 basic drive setup adjustments

Advertising
background image

Table 4.9 Motor Switching and Accel/Decel Time Combinations

Accel/Decel Time 1 (H1-oo = 7)

Motor 1 Selected

(Terminal set to H1-oo = 16 OFF)

Motor 2 Selected

(Terminal set to H1-oo = 16 ON)

Accel

Decel

Accel

Decel

Open

C1-01

C1-02

C1-05

C1-06

Closed

C1-03

C1-04

C1-07

C1-08

Switching Accel/Decel Times by a Frequency Level

The drive can switch between different acceleration and deceleration times automatically. The drive will switch from accel/

decel time 4 in C1-07 and C1-08 to the default accel/decel time in C1-01 and C1-02 (C1-05 and C1-06 for motor 2) when the

output frequency exceeds the frequency level set to parameter C1-11. When the frequency falls below this level, the accel/

decel times are switched back.

Figure 4.22

shows an operation example.

Note:

Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by the frequency level set to C1-11.

For example, if accel/decel time 2 is selected, the drive will use only accel/decel time 2; it will not switch from accel/decel time 4 to the

selected one.

Output Frequency

C1-11

Accel/Decel Time

Switch Frequency

C1-07

setting

When the output frequency C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)

C1-01

setting

C1-02

setting

C1-08

setting

Figure 4.22 Accel/Decel Time Switching Frequency

n

C6-01: Drive Duty Mode Selection

The drive has two different duty modes from which to select based on the load characteristics. The drive rated current, overload

capacity, and maximum output frequency will change depending upon the duty mode selection. Use parameter C6-01 to select

Heavy Duty (HD) or Normal Duty (ND) for the application.

Refer to Heavy Duty and Normal Duty Ratings on page 248

for details about the rated current.

No.

Parameter Name

Setting Range

Default

C6-01

Duty Mode Selection

0, 1

1 (ND)

Table 4.10 Differences between Heavy Duty and Normal Duty

Characteristics

Heavy Duty Rating (HD)

Normal Duty Rating (ND)

C6-01

0

1

Performance

100 %

100 %

0

Motor Speed

Rated Load

Overload

150 %

Motor Speed

0

100 %

100 %

120 %

Rated Load

Overload

Application

Use Heavy Duty Rating for applications requiring a high

overload tolerance with constant load torque, such as

extruders and conveyors.

Use Normal Duty Rating for applications in which the torque

requirements drop along with the speed, such as fans and

pumps where a high overload tolerance is not required.

Overload capability (oL2)

150% of drive rated Heavy Duty current for 60 s

120% of drive rated Normal Duty current for 60 s

Stall Prevention during

Acceleration (L3-02)

150%

120%

Stall Prevention during

Run (L3-06)

150%

120%

Default Carrier Frequency

2 kHz

2 kHz Swing PWM

Note:

Changing the Duty Mode selection automatically changes the maximum size motor that the drive can run, sets the E2-oo parameters to

appropriate values (E4-oo for motor 2), and recalculates parameter settings determined by motor capacity (e.g., b8-04, L2-03, n5-02,

L3-24, C5-17, and C5-37).

4.6 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

167

4

Start-Up Programming & Operation