For more information on digital input functions, 6 basic drive setup adjustments – Yaskawa CIMR-AU 200V Drives User Manual

Page 176

Advertising
background image

Setting

Function

Page

61

External Speed Search Command 1

62

External Speed Search Command 2

63

Field Weakening

65

KEB Ride-Thru 1 (N.C.)

66

KEB Ride-Thru 1 (N.O.)

67

Communications Test Mode

68

High Slip Braking (HSB)

6A

Drive Enabled

71

Speed/Torque Control Switch

72

Zero Servo

75

Up 2 Command

76

Down 2 Command

Setting

Function

Page

77

ASR Gain Switch

78

External Torque Reference Polarity Inversion

7A

KEB Ride-Thru 2 (N.C.)

7B

KEB Ride-Thru 2 (N.O.)

7C

Short Circuit Braking (N.O.)

7D

Short Circuit Braking (N.C.)

7E

Forward/Reverse Detection (V/f control with

simple PG)

7F

PID Bi-directional Enable (No function)

90 to 97 DriveWorksEZ Digital Input 1 to 8

9F

DriveWorksEZ Disabled

Setting 0: 3-Wire Sequence

The digital input programmed for 3-Wire control becomes the forward/reverse directional input, S1 becomes the Run command

input, and S2 becomes the Stop command input.
The drive starts the motor when the input S1 set for the Run command closes for longer than 2 ms. The drive stops the operation

when the Stop input S2 is released. When the digital input programmed for a forward/reverse operation is open, the drive is

set for forward operation. When the digital input is closed, the drive is set for reverse operation.

Note:

Input the Run and Stop commands via S1 and S2 when selecting a 3-Wire sequence.

S1

S2

S5

SN

Run Command (Runs when Closed)

DRIVE

Stop Switch

(N.C.)

Run Switch

(N.O.)

Stop Command (Stops when Open)

FWD/REV (Multi-Function Input)

(H1-05 = 0)
Standard Digital Input Common

Figure 4.25 3-Wire Sequence Wiring Diagram

Figure 5.61

2 ms min.

Run command

Can be
ON or OFF

2 ms min.

ON (reverse)

d

r

a

w

o

F

p

o

t

S

e

s

r

e

v

e

R

p

o

t

S

Can be either ON or OFF

OFF (forward)

Forward

Motor speed

Forward/reverse
command

Stop command

Figure 4.26 3-Wire Sequence

Note:

1. The Run command must be closed for more than 2 ms.
2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate

that protective functions are operating. If required by the application, set b1-17 to 1 to automatically issue the Run command upon drive

power up.

WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before applying

power to the drive. Failure to comply could result in death or serious injury from moving equipment.

WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence

but set up for 2-Wire sequence (default). Make sure b1-17 is set to “0” (drive does not accept a Run command active at power up). When

initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.

4.6 Basic Drive Setup Adjustments

176

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide