L2: momentary power loss ride-thru – Yaskawa CIMR-AU 200V Drives User Manual

Page 314

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L1-17

(0442)

Motor 2 Thermistor

Selection (NTC)

M2 OH5 Fault Sel

0: Disabled

1: Enabled

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 0

Range: 0, 1

L1-18

(0443)

Motor 2 Overheat

Temperature

M2 OH5 level

Sets the temperature for motor 1 that triggers an overheat fault

(oH5).

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 120 °C

Min.: 50

Max.: 200

L1-19

(0444)

Operation at Thermistor

Disconnect (THo)

(NTC)

Tho Stop sel

Determines drive response when a thermistor disconnect fault

(THo) occurs.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time set

to C1-09)

3: Alarm only (“THo” will flash)

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 3

Range: 0 to 3

L1-20

(0445)

Operation at Motor

Overheat (oH5)

OH5 Stop sel

Determines drive response when a motor overheat fault (oH5)

occurs.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time set

to C1-09)

3: Alarm only (“oH5” will flash)

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 1

Range: 0 to 3

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Available in drive software versions PRG: 1019 and later.
<3> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.

u

L2: Momentary Power Loss Ride-Thru

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L2-01

(0485)

Momentary Power Loss

Operation Selection

PwrL Selection

0: Disabled

1: Enbl with Timer

2: Enbl whl CPU act

3: KEB Mode

4: KEB Stop Mode

5: KEB Decel to Stp

0: Disabled. Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02. Uv1 will be detected if

power loss is longer than L2-02.

2: Recover as long as CPU has power. Uv1 is not detected.

3: KEB deceleration for the time set to L2-02.

4: KEB deceleration as long as CPU has power.

5: KEB deceleration to stop.

Default: 0

Range: 0 to 5

L2-02

(0486)

Momentary Power Loss

Ride-Thru Time

PwrL Ridethru t

Sets the Power Loss Ride-Thru time. Enabled only when L2-01

= 1 or 3.

Default:

<1>

Min.: 0.0 s

Max.: 25.5 s

L2-03

(0487)

Momentary Power Loss

Minimum Baseblock

Time

PwrL Baseblock t

Sets the minimum wait time for residual motor voltage decay

before the drive output reenergizes after performing Power Loss

Ride-Thru.

Increasing the time set to L2-03 may help if overcurrent or

overvoltage occur during Speed Search or during DC Injection

Braking.

Default:

<1>

Min.: 0.1 s

Max.: 5.0 s

L2-04

(0488)

Momentary Power Loss

Voltage Recovery Ramp

Time

PwrL V/F Ramp t

Sets the time for the output voltage to return to the preset V/f

pattern during Speed Search.

Default:

<1>

Min.: 0.0 s

Max.: 5.0 s

L2-05

(0489)

Undervoltage Detection

Level (Uv1)

PUV Det Level

Sets the DC bus undervoltage trip level.

Default: 190
Vdc

<2> <3>

Min.: 150 Vdc
Max.: 210 Vdc

<3>

B.8 L: Protection Function

314

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide