Table 4.6 Analog Input Settings for Frequency Reference Using Voltage Signals

Terminal

Signal Level

Parameter Settings

Notes

Signal Level

Selection

Function Selection

Gain

Bias

A1

0 to 10 Vdc

H3-01 = 0

H3-02 = 0

(Frequency Reference Bias)

H3-03

H3-04

-10 to +10 Vdc

H3-01 = 1

A2

0 to 10 Vdc

H3-09 = 0

H3-10 = 0

(Frequency Reference Bias)

H3-11

H3-12

Set DIP switch S1 on the

terminal board to “V” for

voltage input.

-10 to +10 Vdc

H3-09 = 1

A3

0 to 10 Vdc

H3-05 = 0

H3-06 = 0

(Frequency Reference Bias)

H3-07

H3-08

Set DIP switch S4 on the

terminal board to “AI”.

-10 to +10 Vdc

H3-05 = 1

Drive

A1 Analog Input 1

0 to 10 V

AC Analog input common

2 k

+V

-V

10.5 V, 20 mA power supply

-10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

Drive

A1 Analog Input 1

AC Analog input common

+V

-V

10.5 V, 20 mA power supply

-10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

4 k

-10 to 10 V

OR

Figure 4.8 Setting the Frequency Reference as a Voltage Signal at Terminal A1

Use the wiring example shown in the figure above for any other analog input terminals. When using input A2 make sure DIP

switch S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to

Table 4.7

to set terminal A2 for current input.

Table 4.7 Analog Input Settings for Frequency Reference Using a Current Signal

Terminal

Signal

Level

Parameter Settings

Notes

Signal Level

Selection

Function

Selection

Gain

Bias

A2

4 to 20 mA

H3-09 = 2

H3-10 = 0

(Frequency Bias)

H3-11

H3-12

Make sure to set DIP switch S1 on

the terminal board to “I” for

current input.

0 to 20 mA

H3-09 = 3

Drive

A1 Analog Input 1

0 or 4 to 20 mA

AC Analog input common

+V

-V

10.5 V, 20 mA power supply

-10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

DIP switch S1

V

I

Figure 4.9 Setting the Frequency Reference as a Current Signal to Terminal A2

Switching between Main/Auxiliary Frequency References

The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs.

Refer

to Multi-Step Speed Selection on page 168

for details on using this function.