Yaskawa CIMR-AU 200V Drives User Manual

Page 340

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-18

(07DA)

Frequency Reference

Source Selection

Reference Source

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

1 = Reference 1 (b1-01)

2 = Reference 2 (b1-15)

Y-nn: indicates the reference source

0-01 = Digital operator

1-00 = Analog (Not displayed in models 4A0930 and 4A1200)

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

1-03 = Analog (terminal A3)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

5-01 = Pulse input

7-01 = DWEZ

9-01 = Up/Down Command (Not displayed in models 4A0930

and 4A1200)

No signal output

available

U4-19

(07DB)

Frequency Reference

from MEMOBUS/

Modbus Comm.

MEMOBUS Freq Ref

Displays the frequency reference provided by MEMOBUS/

Modbus (decimal).

No signal output

available

0.01%

U4-20

(07DC)

Option Frequency

Reference

Option Freq Ref

Displays the frequency reference input by an option card

(decimal).

No signal output

available

U4-21

(07DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

1 = Reference 1 (b1-02)

2 = Reference 2 (b1-16)

Y: Input power supply data

0 = Digital operator

1 = External terminals

3 = MEMOBUS/Modbus communications

4 = Communication option card

7 = DWEZ

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to

REMOTE operation

03: Waiting for soft charge bypass contactor after power up (Uv

or Uv1 flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, digital operator)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during

baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(07DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal

number.

No signal output

available

U4-23

(07DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit

hexadecimal number.

No signal output

available

U4-32

(07FB)

Motor Temperature

(NTC)

Moter temp (NTC)

Displays the motor temperature (NTC).

U4-32 will display “20 °C” when a multi-function analog input

is not set for motor thermistor input (H1-oo = 17H).

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

200 °C

1 °C

U4-37

(1044)

oH Alarm Location

Monitor

OH Alarm Axis

Displays the module where the oH alarm occurred as a binary

number.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

U4-38

(1045)

FAn Alarm Location

Monitor

FAN Alarm Axis

Displays the module where the FAn alarm occurred as a binary

number.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

B.13 U: Monitors

340

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

Advertising