U2: fault trace – Yaskawa CIMR-AU 200V Drives User Manual

Page 337

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog

Output Level

Unit

U1-25

(004D)

Software Number

(Flash)

CPU 1 SW Number

FLASH ID

No signal output

available

U1-26

(005B) Software No. (ROM)

CPU 2 SW Number

ROM ID

No signal output

available

U1-27

(07A8) Message ID (OPR)

MessageID (OPR)

OPR ID

No signal output

available

U1-28

(07A9) Message ID (INV)

MessageID (INV)

INV ID

No signal output

available

U1-29

(07AA) Software No. (PWM)

CPU 3 SW Number

PWM ID

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

<1> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

<2> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using

MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”

<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> In V/f and V/f w/PG control modes, 10 V = drive capacity (kW). In OLV, CLV, OLV/PM, AOLV/PM, and CLV/PM control modes, 10 V = motor

rated power (E2-11) (kW).

u

U2: Fault Trace

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U2-01

(0080) Current Fault

Current Fault

Displays the current fault.

No signal output

available

U2-02

(0081) Previous Fault

Last Fault

Displays the previous fault.

No signal output

available

U2-03

(0082)

Frequency Reference at

Previous Fault

Frequency Ref

Displays the frequency reference at the previous fault.

No signal output

available

0.01 Hz

U2-04

(0083)

Output Frequency at

Previous Fault

Output Freq

Displays the output frequency at the previous fault.

No signal output

available

0.01 Hz

U2-05

(0084)

Output Current at

Previous Fault

Output Current

Displays the output current at the previous fault.

Note:

The unit is expressed in 1 A for models 4A0930

and 4A1200.

No signal output

available

<1>
<2>

U2-06

(0085)

Motor Speed at Previous

Fault

Motor Speed

Displays the motor speed at the previous fault.

No signal output

available

0.01 Hz

U2-07

(0086)

Output Voltage at

Previous Fault

Output Voltage

Displays the output voltage at the previous fault.

No signal output

available

0.1 Vac

U2-08

(0087)

DC Bus Voltage at

Previous Fault

DC Bus Voltage

Displays the DC bus voltage at the previous fault.

No signal output

available

1 Vdc

U2-09

(0088)

Output Power at

Previous Fault

Output kWatts

Displays the output power at the previous fault.

No signal output

available

0.1 kW

U2-10

(0089)

Torque Reference at

Previous Fault

Torque Reference

Displays the torque reference at the previous fault.

No signal output

available

0.1%

U2-11

(008A)

Input Terminal Status at

Previous Fault

Input Term Sts

Displays the input terminal status at the previous fault. Displayed

as in U1-10.

No signal output

available

U2-12

(008B)

Output Terminal Status

at Previous Fault

Output Term Sts

Displays the output status at the previous fault. Displayed as in

U1-11.

No signal output

available

U2-13

(008C)

Drive Operation Status at

Previous Fault

Inverter Status

Displays the operation status of the drive at the previous fault.

Displayed as in U1-12.

No signal output

available

U2-14

(008D)

Cumulative Operation

Time at Previous Fault Elapsed time

Displays the cumulative operation time at the previous fault.

No signal output

available

1 h

B.13 U: Monitors

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

337

B

Parameter List