Refer to wire gauges and tightening, Wire gauge and torque specifications are listed in, Table 7.9 – Yaskawa CIMR-AU 200V Drives User Manual

Page 244

Advertising
background image

Table 7.9 Wire Gauges and Tightening Torques of PG-X3 Option

Terminal

Signal

Screw Size

Tightening

Torque N

m

(in

lb)

Bare Cable

Crimp Terminals

Wire Type

Recomm.

Gauge mm

2

Applicable

Gauges mm

2

Recomm.

Gauge mm

2

Applicable

Gauges mm

2

A+, A–, B+, B–,

Z+, Z–, SD, FE,

IP, IG

M2

0.22 to 0.25

(1.95 to 2.21)

0.75 (18 AWG)

Stranded wire:

0.25 to 1.0

(24 to 17 AWG)

Solid wire:

0.25 to 1.5

(24 to 16 AWG)

0.5 (20 AWG)

0.25 to 0.5

(24 to 20 AWG)

Shielded twisted

pair, etc.

a+, a–, b+, b–, z+,

z–, SG

Shielded cable,

etc.

PG-X3 Crimp Terminals

Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications listed

in

Table 7.10

for wiring to ensure proper connections.

Note:

Properly trim wire ends so loose wire ends do not extend from the crimp terminals.

Table 7.10 Crimp Terminal Sizes

Wire Gauge

mm

2

Phoenix Contact

Model

L mm (in)

d1 mm (in)

d2 mm (in)

d1

d2

6 mm

L

0.25 (24 AWG)

AI 0.25 - 6YE

10.5 (13/32)

0.8 (1/32)

2 (5/64)

0.34 (22 AWG)

AI 0.34 - 6TQ

10.5 (13/32)

0.8 (1/32)

2 (5/64)

0.5 (20 AWG)

AI 0.5 - 6WH

14 (9/16)

1.1 (3/64)

2.5 (3/32)

Replacing the Drive Covers and Digital Operator and Checking for Proper Motor Rotation

1.

Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to the

outside to provide adequate space for the wiring. In these cases, using diagonal cutting pliers, cut out the perforated

openings on the left side of the drive front cover. Sharp edges along the cut out should be smoothed down with a file

or sand paper to prevent any damage to the wires.
Route the communication wiring inside the enclosure for drives that do not require routing through the front cover.

Refer to

Table 7.11

and

Figure 7.13

to determine the proper wire routing by drive model.

Table 7.11 Communication Wire Routing Selection

Drive Series

Model

Wire Routing <1>

Through Front

Cover

Inside Drive

A1000

Models 2A0004 to 2A0040;

4A0002 to 4A0023;

5A0003 to 5A0011

Figure 7.13

(A)

A1000

Models 2A0056 and above;

4A0031 and above;

5A0023 and above

Figure 7.13

(B)

<1> Refer to

Figure 7.13

for examples of the different wire routing techniques.

7.1 Option Card Installation

244

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide

Advertising